Terminal sizes:
R0...R3: 0.2...2.5 mm
0.14...1.5 mm
R5...R9: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
Notes:
1)
The signal source is powered externally. See the manufacturer's instructions. To use sensors
supplied by the drive aux. voltage output, see chapter Electrical installation, section
Connection examples of two-wire and three-wire sensors in the Hardware manual of the
drive.
2)
If Constant frequency is activated it overrides the reference from the PID controller output.
3)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
4)
Connected with jumpers at the factory.
5)
Note: Use shielded twisted-pair cables for digital signals.
Input signals
•
Analog reference (AI1)
•
Actual feedback from PID (AI2)
•
Start/Stop selection, PID (DI1)
•
Constant setpoint 1 (DI2)
•
Constant setpoint 1 (DI3)
•
Constant frequency 1 (DI4)
•
Run enable (DI5)
Output signals
•
Analog output AO1: Output frequency
•
Analog output AO2: Motor current
•
Relay output 1: Ready run
•
Relay output 2: Running
•
Relay output 3: Fault (-1)
2
(terminals +24V, DGND, DCOM, B+, A-)
2
(terminals DI, AI, AO, AGND, RO, STO)
2
(all terminals)
Control macros 75