ABB ACS580 Firmware Manual page 369

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

Code
Warning / Aux. code
(hex)
A8B1
Signal supervision
(Editable message text)
Programmable warning:
32.16 Supervision 2 action
A8B2
Signal supervision
(Editable message text)
Programmable warning:
32.26 Supervision 3 action
A8B3
Signal supervision
(Editable message text)
Programmable warning:
32.36 Supervision 4 action
A8B4
Signal supervision
(Editable message text)
Programmable warning:
32.46 Supervision 5 action
A8B5
Signal supervision
(Editable message text)
Programmable warning:
32.56 Supervision 6 action
A8C0
ULC invalid speed
table
A8C1
ULC overload warning
A8C4
ULC underload
warning
A8C5
ULC invalid underload
table
A8C6
ULC invalid overload
table
A8C8
ULC invalid frequency
table
A981
External warning 1
(Editable message text)
Programmable warning:
31.01 External event 1
source
31.02 External event 1
type
A982
External warning 2
(Editable message text)
Programmable warning:
31.03 External event 2
source
31.04 External event 2
type
Cause
Warning generated by the
signal supervision function 2.
Warning generated by the
signal supervision function 3.
Warning generated by the
signal supervision function 4.
Warning generated by the
signal supervision function 5.
Warning generated by the
signal supervision function 6.
User load curve: X-axis points
(speed) are not valid.
User load curve: Signal has
been too long over the
overload curve.
User load curve: Signal has
been too long under the
underload curve.
User load curve: Underload
curve points are not valid.
User load curve: Overload
curve points are not valid.
User load curve: X-axis points
(frequency) are not valid.
Fault in external device 1.
Fault in external device 2.
Fault tracing 365
What to do
Check the source of the warning
(parameter
32.17 Supervision 2
Check the source of the warning
(parameter
32.27 Supervision 3
Check the source of the warning
(parameter
32.37 Supervision 4
Check the source of the warning
(parameter
32.47 Supervision 5
Check the source of the warning
(parameter
32.57 Supervision 6
Check that points fulfill conditions. See
parameter
37.11 ULC speed table point
1.
See parameter
37.03 ULC overload
actions.
See parameter
37.04 ULC underload
actions.
Check that points fulfill conditions. See
parameter
37.21 ULC underload point
Check that points fulfill conditions. See
parameter
37.31 ULC overload point
Check that points fulfill conditions. -
500.0 Hz <
37.16
<
37.17
37.19
<
37.20
< 500.0 Hz. See
parameter
37.16 ULC frequency table
point
1.
Check the external device.
Check setting of parameter
External event 1
source.
Check the external device.
Check setting of parameter
External event 2
source.
signal).
signal).
signal).
signal).
signal).
1.
1.
<
37.18
<
31.01
31.03

Hide quick links:

Advertisement

Table of Contents
loading