Terminal sizes:
R0...R3: 0.2...2.5 mm
0.14...1.5 mm
R5...R9: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
Notes:
1)
The signal source is powered externally. See the manufacturer's instructions. To use sensors
supplied by the drive aux. voltage output, see chapter Electrical installation, section
Connection examples of two-wire and three-wire sensors in the Hardware manual of the
drive.
2)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
3)
Connected with jumpers at the factory.
4)
Note: Use shielded twisted-pair cables for digital signals.
Input signals
Setpoint for PID (AI1)
Actual feedback from PID (AI2)
Start/Stop selection, EXT1 (DI1)
Run enable (DI2)
EXT1/EXT2 selection (DI3)
Start/Stop selection, EXT2 (DI6)
Output signals
Analog output AO1: Output frequency
Analog output AO2: Motor current
Relay output 1: Running
Relay output 2: Fault (-1)
Relay output 3: PFC2 (first PFC auxiliary motor)
2
(terminals +24V, DGND, DCOM, B+, A-)
2
(terminals DI, AI, AO, AGND, RO, STO)
2
(all terminals)
Control macros 79