198 Parameters
No.
Name/Value
22.56
Critical speed 3 low
-30000.00...
30000.00 rpm
22.57
Critical speed 3
high
-30000.00...
30000.00 rpm
22.71
Motor
potentiometer
function
Disabled
Enabled (init at
power-up)
Enabled (resume at
power-up)
Enabled (init to
actual)
22.72
Motor
potentiometer initial
value
-32768.00...
32767.00
22.73
Motor
potentiometer up
source
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
Timed function 1
Timed function 2
Timed function 3
Description
Defines the low limit for critical speed range 3.
Note: This value must be less than or equal to the value of
22.57 Critical speed 3
high.
Low limit for critical speed 3.
Defines the high limit for critical speed range 3.
Note: This value must be greater than or equal to the value of
22.56 Critical speed 3
low.
High limit for critical speed 3.
Activates and selects the mode of the motor potentiometer.
See section
Speed control performance figures
Motor potentiometer is disabled and its value set to 0.
When enabled, the motor potentiometer first adopts the value
defined by parameter
22.72 Motor potentiometer initial
The value can then be adjusted from the up and down
sources defined by parameters
source
and
22.74 Motor potentiometer down
A power cycle will reset the motor potentiometer to the
predefined initial value (22.72).
As
Enabled (init at
power-up), but the motor potentiometer
value is retained over a power cycle.
Whenever another reference source is selected, the value of
the motor potentiometer follows that reference. After the
source of reference returns to the motor potentiometer, its
value can again be changed by the up and down sources
(defined by
22.73
and 22.74).
Defines an initial value (starting point) for the motor
potentiometer. See the selections of parameter
potentiometer
function.
Initial value for motor potentiometer.
Selects the source of motor potentiometer up signal.
0 = No change
1 = Increase motor potentiometer value. (If both the up and
down sources are on, the potentiometer value will not
change.)
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Combined timer status
Bit 1 of
34.01 Combined timer status
Bit 2 of
34.01 Combined timer status
(page 102).
value.
22.73 Motor potentiometer up
source.
22.71 Motor
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(see page 240).
(see page 240).
(see page 240).
Def/FbEq16
0.00 rpm
See par.
46.01
0.00 rpm
See par.
46.01
Disabled
0
1
2
3
0.00
1 = 1
Not selected
0
1
2
3
4
5
6
7
18
19
20

Hide quick links: