ABB ACS580 Firmware Manual page 273

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
DI6
Timed function 1
Timed function 2
Timed function 3
Supervision 1
Supervision 2
Supervision 3
Other [bit]
40.43
Set 1 sleep level
0.0...32767.0
40.44
Set 1 sleep delay
0.0...3600.0 s
40.45
Set 1 sleep boost
time
0.0...3600.0 s
40.46
Set 1 sleep boost
step
0.0...32767.0 PID
customer units
40.47
Set 1 wake-up
deviation
-32768.00...
32767.00 PID
customer units
40.48
Set 1 wake-up
delay
0.00...60.00 s
Description
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Combined timer status
Bit 1 of
34.01 Combined timer status
Bit 2 of
34.01 Combined timer status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Defines the start limit for the sleep function. If the value is 0.0,
set 1 sleep mode is disabled.
The sleep function compares the motor speed to the value of
this parameter. If the motor speed remains below this value
longer than the sleep delay defined by
delay, the drive enters the sleep mode and stops the motor.
Sleep start level.
Defines a delay before the sleep function actually becomes
enabled, to prevent nuisance sleeping.
The delay timer starts when the sleep mode is enabled by
parameter
40.43 Set 1 sleep
mode is disabled.
Sleep start delay.
Defines a boost time for the sleep boost step. See parameter
40.46 Set 1 sleep boost
Sleep boost time.
When the drive is entering sleep mode, the process setpoint
is increased by this value for the time defined by parameter
40.45 Set 1 sleep boost
If active, sleep boost is aborted when the drive wakes up.
Sleep boost step.
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay
Set 1 wake-up
delay), the drive wakes up.
See also parameter
40.31 Set 1 deviation
Wake-up level (as deviation between process setpoint and
feedback).
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter
deviation.
The delay timer starts when the deviation exceeds the wake-
up level
(40.47 Set 1 wake-up
deviation falls below the wake-up level.
Wake-up delay.
status, bit 5).
(see page 240).
(see page 240).
(see page 240).
(see page 234).
(see page 234).
(see page 234).
on page 136). -
40.44 Set 1 sleep
level, and resets when the sleep
step.
time.
inversion.
40.47 Set 1 wake-up
deviation), and resets if the
Parameters 269
Def/FbEq16
7
18
19
20
21
22
23
0.0
1 = 1
60.0 s
1 = 1 s
0.0 s
1 = 1 s
0.0 PID
customer
units
1 = 1 PID
customer unit
0.00 PID
customer
units
(40.48
1 = 1 PID
customer unit
0.50 s
1 = 1 s

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents