ABB ACS580 Firmware Manual page 291

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
50.08
FBA A actual 2 type
Speed or frequency
Transparent
General
Torque
Speed
Frequency
50.09
FBA A SW
transparent source
Not selected
Other
50.10
FBA A act1
transparent source
Not selected
Other
50.11
FBA A act2
transparent source
Not selected
Other
50.12
FBA A debug mode
Disable
Fast
Normal
50.13
FBA A control word
00000000h...
FFFFFFFFh
Description
Selects the type and scaling of actual value 2 transmitted to
the fieldbus network through fieldbus adapter A. The scaling
of the value is defined by parameters 46.01...46.04,
depending on which actual value type is selected by this
parameter.
Type and scaling is chosen automatically according to the
currently active operation mode as follows:
Operation mode
(see par. 19.01)
Speed control
Torque control
Frequency control
No scaling is applied.
Generic reference without a specific unit.
The scaling is defined by parameter
The scaling is defined by parameter
The scaling is defined by parameter
Selects the source of the fieldbus status word when
parameter
50.06 FBA A SW sel
No source selected.
Source selection (see
Terms and abbreviations
When parameter
50.07 FBA A actual 1 type
Transparent, this parameter selects the source of actual value
1 transmitted to the fieldbus network through fieldbus adapter
A.
No source selected.
Source selection (see
Terms and abbreviations
When parameter
50.08 FBA A actual 2 type
Transparent, this parameter selects the source of actual value
2 transmitted to the fieldbus network through fieldbus adapter
A.
No source selected.
Source selection (see
Terms and abbreviations
This parameter enables debug mode. Displays raw
(unmodified) data received from and sent to fieldbus adapter
A in parameters 50.13...50.18.
Debug mode disabled.
Debug mode enabled. Cyclical data update is as fast as
possible which increases CPU load on the drive.
Debug mode is enabled but data update cycle is slow enough
to enable normal operations.
Displays the raw (unmodified) control word sent by the
master (PLC) to fieldbus adapter A if debugging is enabled by
parameter
50.12 FBA A debug
This parameter is read-only.
Control word sent by master to fieldbus adapter A.
Actual value 2 type
Torque
Torque
Torque
46.03 Torque
scaling.
46.01 Speed
scaling.
46.02 Frequency
scaling. 5
is set to
Transparent
mode.
on page 136). -
is set to
on page 136). -
is set to
on page 136). -
mode.
Parameters 287
Def/FbEq16
Speed or
frequency
0
1
2
3
4
Not selected
-
Not selected
-
Not selected
-
Normal
0
1
2
-
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents