Abb Standard Macro; Default Control Connections For The Abb Standard Macro - ABB ACS580 Firmware Manual

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

60 Control macros

ABB standard macro

This is the default macro. It provides a general purpose, 2-wire I/O configuration with three
constant speeds. One signal is used to start or stop the motor and another to select the
direction. The ABB standard macro uses scalar control; for vector control, use the ABB standard
(vector) macro (page 62).

Default control connections for the ABB standard macro

1...10 kohm
max.
500 ohm
5)
4)
See the notes on
the next page.
S1
AI1 U/I
S2
AI2 U/I
XI
Reference voltage and analog inputs and outputs
1
2
3
AGND
4
5
6
AGND
7
8
9
AGND
S3
AO1 I/U
3)
X2 & X3
Aux. voltage output and programmable digital inputs
10
11
DGND
4)
12
DCOM
13
14
15
16
17
18
X6, X7, X8 Relay outputs
19
RO1C
20
21
22
RO2C
23
24
25
RO3C
26
27
X5
EIA-485 Modbus RTU
29
30
31
DGND
S4
TERM
S5
X4
Safe torque off
34
35
4)
36
SGND
37
38
X10
24 V AC/DC
40
24 V AC/DC- in R5...R9 only: Ext. 24V AC/DC input to power up the
41
24 V AC/DC+ in
Voltage/Current selection for AI1:
Voltage/Current selection for AI2:
SCR
Signal cable shield (screen)
AI1
Output frequency reference: 0...10 V
Analog input circuit common
+10V
Reference voltage 10 V DC
AI2
Not configured
Analog input circuit common
AO1
Output frequency: 0...20 mA
AO2
Motor current: 0...20 mA
Analog output circuit common
Voltage/Current selection for AO1:
+24V
Auxiliary voltage output +24 V DC, max. 250 mA
Auxiliary voltage output common
Digital input common for all
DI1
Stop (0) / Start (1)
DI2
Forward (0) / Reverse (1)
DI3
Constant frequency selection
DI4
Constant frequency selection
DI5
Ramp set 1 (0) / Ramp set 2 (1)
DI6
Not configured
Ready run
RO1A
250 V AC / 30 V DC
2 A
RO1B
Running
250 V AC / 30 V DC
RO2A
2 A
RO2B
Fault (-1)
250 V AC / 30 V DC
RO3A
2 A
RO3B
B+
Embedded Modbus RTU (EIA-485). See chapter
Fieldbus control through the embedded fieldbus
A-
interface (EFB)
Serial data link termination switch
BIAS
Serial data link bias resistors switch
OUT1
Safe torque off. Factory connection. Both circuits
OUT2
must be closed for the drive to start. See chapter
The Safe torque off function in the Hardware
IN1
manual of the drive.
IN2
control unit when the main supply is disconnected.
U
U
I
1)
1)
2)
on page 377.
I
I
U