Diagnostics

Signal supervision

Six signals can be selected to be supervised by this function. Whenever a supervised
signal exceeds or falls below predefined limits, a bit in
activated, and a warning or fault generated.
The supervised signal is low-pass filtered.
Settings
Parameter group
32 Supervision

Energy saving calculators

This feature consists of the following functionalities:
• An energy optimizer that adjusts the motor flux in such a way that the total system
efficiency is maximized
• A counter that monitors used and saved energy by the motor and displays them in
kWh, currency or volume of CO
• A load analyzer showing the load profile of the drive (see separate section on
page 129).
In addition, there are counters that show energy consumption in kWh of the current
and previous hour as well as the current and previous day.
Note: The accuracy of the energy savings calculation is directly dependent on the
accuracy of the reference motor power given in parameter
Settings
• Menu - Energy efficiency
• Parameter group
• Parameters
01.50 Current hour
day kWh
and
01.53 Previous day kWh

Load analyzer

Peak value logger
The user can select a signal to be monitored by a peak value logger. The logger
records the peak value of the signal along with the time the peak occurred, as well as
motor current, DC voltage and motor speed at the time of the peak. The peak value is
sampled at 2 ms intervals.
Amplitude loggers
The control program has two amplitude loggers.
(page 234).
emissions, and
2
45 Energy efficiency
kWh,
32.01 Supervision status
45.19 Comparison
(page 276).
01.51 Previous hour
on page 140.
Program features 129