128 Program features
Overspeed protection (parameter 31.30)
The user can set overspeed limits by specifying a margin that is added to the
currently-used maximum and minimum speed limits.
Local control loss detection (parameter 49.05)
The parameter selects how the drive reacts to a control panel or PC tool
communication break.
AI supervision (parameters 12.03...12.04)
The parameters select how the drive reacts when an analog input signal moves out of
the minimum and/or maximum limits specified for the input. This can be due to broken
I/O wiring or sensor.

Automatic fault resets

The drive can automatically reset itself after overcurrent, overvoltage, undervoltage
and external faults. The user can also specify a fault that is automatically reset.
By default, automatic resets are off and must be specifically activated by the user.
Settings
• Menu - Primary settings - Advanced functions - Autoreset faults
• Parameters
31.12...31.16
(page 230).