ABB ACS580 Firmware Manual page 193

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
Supervision 3
Timed function 1
Timed function 2
Timed function 3
Other [bit]
21.16
Pre-heating current
0.0...30.0%
21.18
Auto restart time
0.0 s
0.1...10.0 s
21.19
Scalar start mode
Normal
Const time
Automatic
Description
Bit 2 of
32.01 Supervision status
Bit 0 of
34.01 Combined timer status
Bit 1 of
34.01 Combined timer status
Bit 2 of
34.01 Combined timer status
Source selection (see
Terms and abbreviations
Defines the DC current used to heat motor findings.
Pre-heating current.
The motor can be automatically started after a short supply
power failure using the automatic restart function. See section
Automatic restart
(page 120).
When this parameter is set to 0.0 seconds, automatic
restarting is disabled. Otherwise, the parameter defines the
maximum duration of the power failure after which restarting
is attempted. Note that this time also includes the DC
precharging delay.
WARNING! Before you activate the function, make
sure that no dangerous situations can occur. The
function restarts the drive automatically and continues
operation after a supply break.
Automatic restarting disabled.
Maximum power failure duration.
Selects the motor start function for the scalar motor control
mode, ie. when
99.04 Motor control mode
Notes:
• The start function for the vector motor control mode is
selected by parameter
• With permanent magnet motors,
must be used.
• This parameter cannot be changed while the drive is
running.
See also section
DC magnetization
Immediate start from zero speed.
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is defined by parameter
Magnetization
time. This mode should be selected if constant
pre-magnetizing time is required (e.g. if the motor start must
be synchronized with the release of a mechanical brake).
This setting also guarantees the highest possible break-away
torque when the pre-magnetizing time is set long enough.
Note: This mode cannot be used to start into a rotating motor.
WARNING! The drive will start after the set pre-
magnetizing time has passed even if motor
magnetization is not completed. In applications where
a full break-away torque is essential, ensure that the constant
magnetizing time is long enough to allow generation of full
magnetization and torque.
The drive automatically selects the correct output frequency
to start a rotating motor. This is useful for flying starts: if the
motor is already rotating, the drive will start smoothly at the
current frequency.
Note: Cannot be used in multimotor systems.
(see page 234).
(see page 240).
(see page 240).
(see page 240).
on page 136). -
is set to Scalar.
21.01 Vector start
mode.
Automatic
start mode
(page 106).
21.02
Parameters 189
Def/FbEq16
10
11
12
13
0.0%
1 = 1%
10.0 s
0
1 = 1 s
Normal
0
1
2