ABB ACS580 Firmware Manual page 275

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
Supervision 1
Supervision 2
Supervision 3
Other [bit]
40.58
Set 1 increase
prevention
No
Limiting
Ext PID min lim
Ext PID max lim
40.59
Set 1 decrease
prevention
No
Limiting
Ext PID min lim
Ext PID max lim
40.62
PID internal
setpoint actual
-32768.00...
32767.00 PID
customer units
40.91
Feedback data
storage
-327.68...327.67
Description
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Prevention of PID integration term increase for PID set 1.
Increase prevention not in use.
The PID integration term is not increased if the maximum
value for the PID output is reached. This parameter is valid
for the PID set 1.
The process PID integration term is not increased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
The process PID integration term is not increased when the
output of the external PID has reached its maximum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
Prevention of PID integration term decrease for PID set 1.
Decrease prevention not in use.
The PID integration term is not decreased if the minimum
value for the PID output is reached. This parameter is valid
for the PID set 1.
The process PID integration term is not decreased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
The process PID integration term is not decreased when the
output of the external PID has reached its maximum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
Displays the value of the internal setpoint. See the control
chain diagram on page 431.
This parameter is read-only.
Process PID internal setpoint.
Storage parameter for receiving a process feedback value eg.
through the embedded fieldbus interface.
The value can be sent to the drive as Modbus I/O data. Set
the target selection parameter of that particular data
(58.101...58.114) to
Feedback data
feedback 1 source
(or
40.09 Set 1 feedback 2
Feedback
storage.
Storage parameter for process feedback.
Parameters 271
(see page 234).
(see page 234).
(see page 234).
on page 136). -
storage. In
40.08 Set 1
source), select
Def/FbEq16
21
22
23
No
0
1
2
3
No
0
1
2
3
-
1 = 1 PID
customer unit
-
100 = 1