78 Control macros

PFC macro

Pump and fan control logic for controlling multiple pumps or fans through the drive's relay
outputs. To enable the macro, select it in the Primary settings menu or set parameter
Macro select
to PFC.

Default control connections for the PFC macro

1...10 kohm
max.
500 ohm
4)
3)
See the notes on
the next page.
S1
AI1 U/I
S2
AI2 U/I
XI
Reference voltage and analog inputs and outputs
1
2
3
AGND
4
5
6
AGND
7
8
9
AGND
S3
AO1 I/U
2)
X2 & X3
Aux. voltage output and programmable digital inputs
10
11
DGND
5)
12
DCOM
13
14
15
16
17
18
X6, X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
EIA-485 Modbus RTU
29
30
31
DGND
S4
TERM
S5
X4
Safe torque off
34
OUT1
35
OUT2
3)
36
SGND
37
38
X10
24 V AC/DC
40
24 V AC/DC- in R5...R9 only: Ext. 24V AC/DC input to power up the
41
24 V AC/DC+ in
Voltage/Current selection for AI1:
Voltage/Current selection for AI2:
SCR
Signal cable shield (screen)
AI1
PID setpoint source: 0...10 V
Analog input circuit common
+10V
Reference voltage 10 V DC
AI2
Actual PID feedback: 4...20 mA
Analog input circuit common
AO1
Output frequency: 0...20 mA
AO2
Motor current: 0...20 mA
Analog output circuit common
Voltage/Current selection for AO1:
+24V
Auxiliary voltage output +24 V DC, max. 250 mA
Auxiliary voltage output common
Digital input common for all
DI1
Stop (0) / Start (1) (EXT1)
DI2
Run enable; if 0, drive stops
DI3
EXT1 (0) / EXT2 (1): parameter
DI4
Not configured
DI5
Not configured
DI6
Stop (0) / Start (1) (EXT2)
Running
250 V AC / 30 V DC
2 A
Fault (-1)
250 V AC / 30 V DC
2 A
PFC2 (2nd motor=1st aux. motor)
250 V AC / 30 V DC
2 A
B+
Embedded Modbus RTU (EIA-485). See chapter
A-
Fieldbus control through the embedded fieldbus
interface (EFB)
Serial data link termination switch
BIAS
Serial data link bias resistors switch
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start. See chapter
The Safe torque off function in the Hardware
IN1
manual of the drive.
IN2
control unit when the main supply is disconnected.
U
U
1)
I
19.11
on page 377.
96.04
I
I
U

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents