248 Parameters
No.
Name/Value
KTY84 analog I/O
1 × Pt100 analog
I/O
2 × Pt100 analog
I/O
3 × Pt100 analog
I/O
Direct temperature
Description
KTY84 sensor connected to the analog input selected by
parameter
35.14 Temperature 1 AI source
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
Pt100 sensor connected to a standard analog input selected
by parameter
35.14 Temperature 1 AI source
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
The temperature is taken from the source selected by
parameter
35.14 Temperature 1 AI
source is assumed to be degrees Celsius.
and an analog
to
V
(volt).
AO, set the source
Temp sensor 1
and an analog
to
V
(volt).
AO, set the source
Temp sensor 1
I/O, but with two sensors
I/O, but with three sensors
source. The value of the
Def/FbEq16
2
5
6
7
11

Hide quick links:

Advertisement

Table of Contents
loading