266 Parameters
No.
Name/Value
Timed function 3
Supervision 1
Supervision 2
Supervision 3
Other [bit]
40.21
Set 1 internal
setpoint 1
-32768.00...
32767.00 PID
customer units
40.22
Set 1 internal
setpoint 2
-32768.00...
32767.00 PID
customer units
40.23
Set 1 internal
setpoint 3
-32768.00...
32767.00 PID
customer units
40.26
Set 1 setpoint min
-32768.00...
32767.00
40.27
Set 1 setpoint max
-32768.00...
32767.00
40.28
Set 1 setpoint
increase time
0.0...1800.0 s
40.29
Set 1 setpoint
decrease time
0.0...1800.0 s
40.30
Set 1 setpoint
freeze enable
Not selected
Selected
DI1
DI2
DI3
Description
Bit 2 of
34.01 Combined timer status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Internal process setpoint 1. See parameter
internal setpoint
sel1.
Internal process setpoint 1.
Internal process setpoint 2. See parameter
internal setpoint
sel1.
Internal process setpoint 2.
Internal process setpoint 3. See parameter
internal setpoint
sel1.
Internal process setpoint 3.
Defines a minimum limit for the process PID controller
setpoint.
Minimum limit for process PID controller setpoint.
Defines a maximum limit for the process PID controller
setpoint.
Maximum limit for process PID controller setpoint.
Defines the minimum time it takes for the setpoint to increase
from 0% to 100%.
Setpoint increase time.
Defines the minimum time it takes for the setpoint to decrease
from 100% to 0%.
Setpoint decrease time.
Freezes, or defines a source that can be used to freeze, the
setpoint of the process PID controller. This feature is useful
when the reference is based on a process feedback
connected to an analog input, and the sensor must be
serviced without stopping the process.
1 = Process PID controller setpoint frozen
See also parameter
40.38 Set 1 output freeze
Process PID controller setpoint not frozen.
Process PID controller setpoint frozen.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
(see page 240).
(see page 234).
(see page 234).
(see page 234).
on page 136). -
40.19 Set 1
40.19 Set 1
40.19 Set 1
enable.
status, bit 0).
status, bit 1).
status, bit 2).
Def/FbEq16
20
21
22
23
0.00 PID
customer
units
1 = 1 PID
customer unit
0.00 PID
customer
units
1 = 1 PID
customer unit
0.00 PID
customer
units
1 = 1 PID
customer unit
0.00
1 = 1
32767.00
1 = 1
0.0 s
1 = 1
0.0 s
1 = 1
Not selected
0
1
2
3
4