3-Wire Macro; Default Control Connections For The 3-Wire Macro - ABB ACS580 Firmware Manual

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

64 Control macros

3-wire macro

This macro is used when the drive is controlled using momentary push-buttons. It provides three
constant speeds. To enable the macro, select it in the Primary settings menu or set parameter
96.04 Macro select
to 3-wire.

Default control connections for the 3-wire macro

1...10 kohm
max.
500 ohm
5)
4)
See the notes on
the next page.
S1
AI1 U/I
S2
AI2 U/I
XI
Reference voltage and analog inputs and outputs
1
2
3
AGND
4
5
6
AGND
7
8
9
AGND
S3
AO1 I/U
3)
X2 & X3
Aux. voltage output and programmable digital inputs
10
11
DGND
4)
12
DCOM
13
14
15
16
17
18
X6, X7, X8 Relay outputs
19
RO1C
20
21
22
RO2C
23
24
25
RO3C
26
27
X5
EIA-485 Modbus RTU
29
30
31
DGND
S4
TERM
S5
X4
Safe torque off
34
35
4)
36
SGND
37
38
X10
24 V AC/DC
40
24 V AC/DC- in R5...R9 only: Ext. 24V AC/DC input to power up the
41
24 V AC/DC+ in
Voltage/Current selection for AI1:
Voltage/Current selection for AI2:
SCR
Signal cable shield (screen)
AI1
Ext. speed/frequency reference 1: 0...10 V
Analog input circuit common
+10V
Reference voltage 10 V DC
AI2
Not configured
Analog input circuit common
AO1
Output frequency: 0...20 mA
AO2
Motor current: 0...20 mA
Analog output circuit common
Voltage/Current selection for AO1:
+24V
Auxiliary voltage output +24 V DC, max. 250 mA
Auxiliary voltage output common
Digital input common for all
DI1
Start (pulse
DI2
Stop (pulse
DI3
Forward (0) / Reverse (1)
DI4
Constant speed/frequency selection
DI5
Constant speed/frequency selection
DI6
Not configured
Ready run
250 V AC / 30 V DC
RO1A
2 A
RO1B
Running
RO2A
250 V AC / 30 V DC
2 A
RO2B
Fault (-1)
250 V AC / 30 V DC
RO3A
2 A
RO3B
B+
Embedded Modbus RTU (EIA-485). See chapter
Fieldbus control through the embedded fieldbus
A-
interface (EFB)
Serial data link termination switch
BIAS
Serial data link bias resistors switch
OUT1
Safe torque off. Factory connection. Both circuits
OUT2
must be closed for the drive to start. See chapter
The Safe torque off function in the Hardware
IN1
manual of the drive.
IN2
control unit when the main supply is disconnected.
U
U
I
)
)
2)
2)
on page 377.
I
I
1)
U