FC 300 Programming Guide
NB!
Max. output frequency cannot exceed 10% of the inverter switching frequency (par. 14-01
Par. 4-19
Max Output Frequency
cannot be adjusted while the motor is running.
4-20 Torque Limit Factor Source
Option:
[0] *
No function
[2]
Analog in 53
[4]
Analog in 53 inv
[6]
Analog in 54
[8]
Analog in 54 inv
[10]
Analog in X30-11
[12]
Analog in X30-11 inv
[14]
Analog in X30-12
[16]
Analog in X30-12 inv
4-21 Speed Limit Factor SourceOption
Option:
[0] *
No function
[2]
Analog input 53
[4]
Analog input 53 inv
[6]
Analog input 54
[8]
Analog input 54 inv
[10]
Analog input X30-11
[12]
Analog input X30-11 inv
[14]
Analog input X30-12
[16]
Analog input X30-12 inv
3.6.3 4-3* Motor Feedback Monitoring
The parameter group includes monitoring and handling of motor feedback devices as encoders, resolvers etc.
4-30 Motor Feedback Loss Function
Option:
[0]
Disabled
Function:
Select an analog input for scaling the settings in par. 4-16
Torque Limit Generator Mode
par. 4-17
sponding to 0% and 100% are defined in the analog input scaling, e.g. par. group 6-1*. This pa-
rameter is only active when par. 1-00
Loop
.
Function:
Select an analog input for scaling the settings in par. 4-19 from 0% to 100% (or vice versa). The
signal levels corresponding to 0% and 100% are defined in the analog input scaling, e.g. par. group
6-1*. This parameter is only active when par. 1-00
Function:
Select which reaction the frequency converter should take if a feedback fault is detected Closed
Loop. The feedback fault is measured between the feedback (unfiltered) and the frequency that is
sent to the motor (16-13) - compensated for slip. The reaction will be activated if the measured
difference is more than specified in par. 4-31
Motor Feedback Loss Timeout
par. 4-32
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
3 Parameter descriptions
Switching Frequency
Torque Limit Motor Mode
from 0% to 100% (or inverse). The signal levels corre-
Configuration Mode
is in
Speed Open Loop
Configuration Mode
is in
Motor Feedback Speed Error
for the time specified in
.
).
3
and
or
Speed Closed
Torque Mode
.
87