3 Parameter descriptions
3.3.5 1-5* Load Indep. Setting
3
Parameters for setting the load-independent motor settings.
1-50 Motor Magnetisation at Zero Speed
Range:
100 %*
[0 - 300 %]
1-51 Min Speed Normal Magnetising [RPM]
Range:
Application
[10 - 300 RPM]
dependent*
1-52 Min Speed Normal Magnetising [Hz]
Range:
Application
[Application dependant]
dependent*
1-53 Model Shift Frequency
Range:
Application
[Application dependant]
dependent*
52
obtain the offset angle value: After frequency converter start-up apply DC-hold and enter the value
Motor Angle
of par. 16-20
into this parameter.
This parameter is only active when par. 1-10
(Permanent Magnet Motor).
Function:
Use this parameter along with par. 1-51
thermal load on the motor when running at low speed.
Enter a value which is a percentage of the rated magnetizing current. If the setting is too low, the
torque on the motor shaft may be reduced.
Function:
Set the required speed for normal magnetising current. If the speed is set lower than the motor slip
Motor Magnetisation at Zero Speed
speed, par. 1-50
[RPM]
are of no significance.
Use this parameter along with par. 1-50
par. 1-50
Motor Magnetisation at Zero Speed
Function:
Set the required frequency for normal magnetising current. If the frequency is set lower than the
Motor Magnetisation at Zero Speed
motor slip frequency, par. 1-50
Use this parameter along with par. 1-50
par. 1-50
Motor Magnetisation at Zero Speed
Function:
Flux Model shift
Enter the frequency value for shift between two models for determining motor speed. Choose the
value based on settings in par. 1-00
Configuration Mode
are two options: shift between Flux model 1 and Flux model 2; or shift between Variable Current
mode and Flux model 2. This parameter is available for FC 302 only.
This parameter cannot be adjusted while the motor is running.
Flux Model 1 – Flux model 2
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
FC 300 Programming Guide
Motor Construction
is set to
PM, non-salient SPM
Min Speed Normal Magnetising [RPM]
Min Speed Normal Magnetising
and par. 1-51
Motor Magnetisation at Zero Speed
.
is inactive.
Motor Magnetisation at Zero Speed
.
and par. 1-01
Motor Control Principle
[1]
to obtain a different
. See drawing for
. See drawing for
. There