3 Parameter descriptions
3.3.4 1-3* Adv. Motor Data
Parameters for advanced motor data. The motor data in par. 1-30
to run the motor optimally. The default settings are figures based on common motor parameter values from standard motors. If the motor parameters
are not set correctly, a malfunction of the frequency converter system may occur. If the motor data is not known, running an AMA (Automatic Motor
Adaptation) is recommended. See the
the moment of inertia of the rotor and the iron loss resistance (par. 1-36
Par. 1-3* and par. 1-4* cannot be adjusted while the motor is running.
3
Illustration 3.1: Motor equivalent diagram for an asynchronous motor
1-30 Stator Resistance (Rs)
Range:
Application
[Application dependant]
dependent*
1-31 Rotor Resistance (Rr)
Range:
Application
[Application dependant]
dependent*
1-33 Stator Leakage Reactance (X1)
Range:
Application
[Application dependant]
dependent*
1-34 Rotor Leakage Reactance (X2)
Range:
Application
[Application dependant]
dependent*
50
Stator Resistance (Rs)
Automatic Motor Adaptation
section in the Design Guide. The AMA sequence will adjust all motor parameters except
Iron Loss Resistance (Rfe)
Function:
Set the stator resistance value. Enter the value from a motor data sheet or perform an AMA on a
cold motor.
Function:
Fine-tuning R
will improve shaft performance. Set the rotor resistance value using one of these
r
methods:
1.
Run an AMA on a cold motor. The frequency converter will measure the value from the
motor. All compensations are reset to 100%.
2.
Enter the R
value manually. Obtain the value from the motor supplier.
r
3.
Use the R
default setting. The frequency converter establishes the setting on the basis of
r
the motor nameplate data.
Function:
Set the stator leakage reactance of the motor using one of these methods:
1.
Run an AMA on a cold motor. The frequency converter will measure the value from the
motor.
2.
Enter the X
1
3.
Use the X
default setting. The frequency converter establishes the setting on the basis of
1
the motor name plate data.
Function:
Set the rotor leakage reactance of the motor using one of these methods:
1.
Run an AMA on a cold motor. The frequency converter will measure the value from the
motor.
2.
Enter the X
2
3.
Use the X
default setting. The frequency converter establishes the setting on the basis of
2
the motor name plate data.
MG.33.M8.02 - VLT
Motor Poles
to par. 1-39
).
value manually. Obtain the value from the motor supplier.
value manually. Obtain the value from the motor supplier.
®
is a registered Danfoss trademark
FC 300 Programming Guide
must match the relevant motor in order