FC 300 Programming Guide
[0] *
No operation
[52]
MCO 0-20mA
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[113]
PID Clamped Output
[119]
Torque % lim
[130]
Output freq. 4-20mA
[131]
Reference 4-20mA
[132]
Feedback 4-20mA
[133]
Motor cur. 4-20mA
[134]
Torq.% lim 4-20 mA
[135]
Torq.% nom 4-20 mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[138]
Torque 4-20mA
[139]
Bus ctrl. 0-20 mA
When no signal on the analog output.
0 Hz = 0 mA; 100 Hz = 20 mA.
Par. 3-00
Reference Range
[Min - Max] 0% = 0 mA; 100% = 20 mA
Reference Range
Par. 3-00
[-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
Value is taken from par. 16-37
Inv. Max. Current
20 mA.
Example: Inverter norm current (11 kW) = 24 A. 160 % = 38.4 A. Motor norm current = 22 A Read-
out 11.46 mA.
20
mA x
22
A
= 11.46
mA
A
38.4
In case the norm motor current is equal to 20 mA, the output setting of par. 6-62
Max. Scale
is:
I VLT
x
100
Max
38.4
x
100
=
I Motor
22
Norm
The torque setting is related to setting in par. 4-16
The torque is related to the motor torque setting.
Taken from par. 1-20
Motor Power [kW]
Maximum Reference
Taken from par. 3-03
Torque reference related to 160% torque.
Max Output Frequency
In relation to par. 4-19
0 Hz = 4 mA, 100 Hz = 20 mA
Reference Range
Par. 3-00
[Min-Max] 0% = 4 mA; 100% = 20 mA
Par. 3-00
Reference Range
[-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
Inv. Max. Current
Value is taken from par. 16-37
20 mA.
Example: Inverter norm current (11 kW) = 24 A. 160 % = 38.4 A. Motor norm current = 22 A Read-
out 11.46 mA.
mA x
A
16
22
mA
= 9.17
A
38.4
In case the norm motor current is equal to 20 mA, the output setting of par. 6-62
Max. Scale
is:
I VLT
x
100
Max
x
38.4
100
=
I Motor
22
Norm
The torque setting is related to setting in par. 4-16
The torque setting is related to the motor torque setting.
Motor Power [kW]
Taken from par. 1-20
Taken from par. 3-03
Maximum Reference
Torque reference related to 160% torque.
An output value set from fieldbus process data. The output will work independently of internal
functions in the frequency converter.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
3 Parameter descriptions
. Inverter max. current (160% current) is equal to
= 175 %
Torque Limit Motor Mode
.
Maximum Reference
. 20 mA = value in par. 3-03
.
. Inverter max. current (160% current) is equal to
= 175 %
Torque Limit Motor Mode
. 20 mA = Value in par. 3-03
3
Terminal X30/8
.
Terminal X30/8
.
Maximum Reference
.
123