FC 300 Programming Guide
3.8.5 6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for analog input 3 (X30/11) placed on option module MCB 101.
6-30 Terminal X30/11 Low Voltage
Range:
0.07 V*
[Application dependant]
6-31 Terminal X30/11 High Voltage
Range:
10.00 V*
[Application dependant]
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
0.000 N/A*
[-999999.999 - 999999.999 N/A]
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
100.000 N/
[-999999.999 - 999999.999 N/A]
A*
6-36 Term. X30/11 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
3.8.6 6-4* Analog Input 4 MCB 101
Parameter group for configuring the scale and limits for analog input 4 (X30/12) placed on option module MCB 101.
6-40 Terminal X30/12 Low Voltage
Range:
0.07 V*
[Application dependant]
6-41 Terminal X30/12 High Voltage
Range:
10.00 V*
[Application dependant]
6-44 Term. X30/12 Low Ref./Feedb. Value
Range:
0.000 N/A*
[-999999.999 - 999999.999 N/A]
6-45 Term. X30/12 High Ref./Feedb. Value
Range:
100.000 N/
[-999999.999 - 999999.999 N/A]
A*
Function:
Sets the analog input scaling value to correspond to the low reference/feedback value (set in
Term. X30/11 Low Ref./Feedb. Value
par. 6-34
Function:
Sets the analog input scaling value to correspond to the high reference/feedback value (set in
Term. X30/11 High Ref./Feedb. Value
par. 6-35
Function:
Sets the analog input scaling value to correspond to the low voltage value (set in par. 6-30
X30/11 Low Voltage
).
Function:
Sets the analog input scaling value to correspond to the high voltage value (set in par. 6-31
X30/11 High Voltage
).
Function:
A 1
st
order digital low pass filter time constant for suppressing electrical noise on terminal X30/11.
Term. X30/11 Filter Time Constant
Par. 6-36
Function:
Sets the analog input scaling value to correspond to the low reference/feedback value set in
Term. X30/12 Low Ref./Feedb. Value
par. 6-44
Function:
Sets the analog input scaling value to correspond to the high reference/feedback value set in
par. 6-45
Term. X30/12 High Ref./Feedb. Value
Function:
Sets the analog output scaling value to correspond to the low voltage value set in par. 6-40
X30/12 Low Voltage
.
Function:
Sets the analog input scaling value to correspond to the high voltage value set in par. 6-41
X30/12 High Voltage
.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
3 Parameter descriptions
).
).
cannot be changed while the motor is running.
.
.
3
Terminal
Terminal
Terminal
Terminal
119