3 Parameter descriptions
Using an analog input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is too high.
Parameter set-up:
Set par. 1-90
Motor Thermal Protection
Thermistor Source
Set par. 1-93
3
Input
Digital/analog
Digital
Digital
Analog
NB!
Check that the chosen supply voltage follows the specification of the used thermistor element.
1-93 Thermistor Source
Option:
[0] *
None
[1]
Analog input 53
[2]
Analog input 54
[3]
Digital input 18
[4]
Digital input 19
[5]
Digital input 32
[6]
Digital input 33
NB!
This parameter cannot be adjusted while the motor is running.
NB!
Digital input should be set to [0]
62
to
Thermistor Trip
[2]
Analog Input 54
to
[2]
Supply Voltage
Volt
24 V
10 V
10 V
Function:
Select the input to which the thermistor (PTC sensor) should be connected. An analog input option
[1] or [2] cannot be selected if the analog input is already in use as a reference source (selected in
Reference 1 Source
par. 3-15
When using MCB 112, choice [0]
PNP - Active at 24V
MG.33.M8.02 - VLT
Threshold
Cut-out Values
< 6.6 kΩ - > 10.8 kΩ
< 800Ω - > 2.7 kΩ
< 3.0 kΩ - > 3.0 kΩ
Reference 2 Source
, par. 3-16
None
must always be selected.
in par. 5-00.
®
is a registered Danfoss trademark
FC 300 Programming Guide