FC 300 Programming Guide
[52]
Control ready
[53]
Drive ready
[54]
Running
[55]
Reversing
[56]
In range
[60]
On reference
[61]
Below reference, low
[62]
Above ref, high
[65]
Torque limit
[66]
Current limit
[67]
Out of current range
[68]
Below I low
[69]
Above I high
[70]
Out of speed range
[71]
Below speed low
[72]
Above speed high
[75]
Out of feedb. range
[76]
Below feedb. low
[77]
Above feedb. high
[80]
Thermal warning
[82]
Mains out of range
[85]
Warning
[86]
Alarm (trip)
[87]
Alarm (trip lock)
[90]
Bus OK
[91]
Torque limit & stop
[92]
Brake fault (IGBT)
[93]
Mech. brake control
[94]
Safe stop active
[100]
Comparator 0
Control ready
[52] The control board receives supply voltage
Drive ready
[53] The frequency converter is ready for operation and applies a supply signal on the
control board.
Running
[54] The motor is running.
Reversing
[55] The output is high when the frequency converter is running counter clockwise (the
logical product of the status bits "running" AND "reverse")
In range
[56] The motor is running within the programmed current and speed ranges set in
Warning Current Low
par. 4-50
to par. 4-53
On reference
[60] The motor is running on reference.
Below reference, low
[61] The motor is running below the value given in par. 4-54
ence Low
Above reference, high
[62] The motor is running above the value given in par. 4-55
erence High
Torque limit
[65] The torque limit, set in par. 4-16
Limit Generator Mode
, has been exceeded.
Current limit
[66] The motor current limit, set in par. 4-18
Out of current range
[67] The motor current is outside the range set in par. 4-18
Below I low
[68] The motor current is lower than set in par. 4-50
Above I high
[69] The motor current is higher than set in par. 4-51
Out of speed range
[70] The speed is outside the range set in par. 4-52
Warning Speed High
par. 4-53
.
Below speed low
[71] The output speed is lower than the setting in par. 4-52
Above speed high
[72] The output speed is higher than the setting in par. 4-53
High
.
Out of feedb. Range
[75] The feedback is outside the range set in par. 4-56
Low
Warning Feedback High
and par. 4-57
Below feedb. Low
[76] The feedback is below the limit set in par. par. 4-56
Low
.
Above feedb. High
[77] The feedback is above the limit set in par. 4-57
Thermal warning
[80] The thermal warning turns on when the temperature exceeds the limit in the
motor, the frequency converter, the brake resistor or thermistor.
Mains out of range
[82] The mains voltage is outside the specified voltage range.
Warning
[85] A warning is active.
Alarm (trip)
[86] A (trip) alarm is active.
Alarm (trip lock)
[87] A (Trip lock) alarm is active.
Bus OK
[90] Active communication (no time-out) via the serial communication port.
Torque limit & stop
[91] If the frequency converter has received a stop signal and is at the torque
limit, the signal is logic "0".
Brake fault (IGBT)
[92] The brake IGBT is short circuited.
Mech. brake control
[93] The mechanical brake is active.
Comparator 0
[100] The result of comparator 0.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
3 Parameter descriptions
Warning Speed High
.
Torque Limit Motor Mode
or par. 4-17
Current Limit
, has been exceeded.
Warning Current Low
Warning Current High
Warning Speed Low
Warning Speed Low
.
Warning Feedback High
3
Warning Refer-
Warning Ref-
Torque
Current Limit
.
.
.
and
.
Warning Speed
Warning Feedback
Warning Feedback
.
181