FC 300 Programming Guide
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic Rule 0
[71]
Logic Rule 1
[72]
Logic Rule 2
[73]
Logic Rule 3
[74]
Logic Rule 4
[75]
Logic Rule 5
[80]
SL Digital Output A
[81]
SL Digital Output B
[82]
SL Digital Output C
[83]
SL Digital Output D
[84]
SL Digital Output E
[85]
SL Digital Output F
[120]
Local reference active
[121]
Remote reference active
[122]
No alarm
See par. group 13-1*. If Comparator 3 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-1*. If Comparator 4 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-1*. If Comparator 5 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 0 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 1 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 2 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 3 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 4 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 5 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
SL Controller Action
See par. 13-52
Set dig. out. A high
is executed. The output will go low whenever the Smart Logic Action [32] Set
dig. out. A low is executed.
SL Controller Action
See par. 13-52
Set dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [33]
dig. out. A low
is executed.
SL Controller Action
See par. 13-52
Set dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [34]
dig. out. A low
is executed.
SL Controller Action
See par. 13-52
Set dig. out. A
high is executed. The input will go low whenever the Smart Logic Action [35]
dig. out. A low
is executed.
SL Controller Action
See par. 13-52
Set dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [36]
dig. out. A low
is executed.
SL Controller Action
See par. 13-52
Set dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [37]
dig. out. A low
is executed.
Output is high when par. 3-13
Reference Site
Linked to hand auto
at the same time as the LCP is in Hand on mode.
Reference site set in par. 3-13
Reference site: Local par. 3-13 [2]
Reference site: Remote par. 3-13 [1]
Reference site: Linked to Hand/ Auto
Hand
Hand -> off
Auto -> off
Auto
Output is high when par. 3-13
Reference Site = Remote
LCP is in [Auto on] mode. See above.
Output is high when no alarm is present.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
3 Parameter descriptions
. The output will go high whenever the Smart Logic Action [38]
. The input will go high whenever the Smart Logic Action [39]
. The input will go high whenever the Smart Logic Action [40]
. The input will go high whenever the Smart Logic Action [41]
. The input will go high whenever the Smart Logic Action [42]
. The input will go high whenever the Smart Logic Action [43]
= [2] Local or when par. 3-13
Local reference
active [120]
1
0
1
1
0
0
[1] or
Linked to hand/auto
3
Set
Set
Set
Set
Set
Reference Site
= [0]
Remote reference
active [121]
0
1
0
0
0
1
[0] while the