3 Parameter descriptions
8-34 Estimated cycle time
Range:
0 ms*
[0 - 1000000 ms]
8-35 Minimum Response Delay
3
Range:
10 ms*
[Application dependant]
8-36 Max Response Delay
Range:
Application
[Application dependant]
dependent*
8-37 Max Inter-Char Delay
Range:
Application
[Application dependant]
dependent*
3.10.5 8-4* FC MC protocol set
8-40 Telegram selection
Option:
[1] *
Standard telegram 1
[100]
None
[101]
PPO 1
[102]
PPO 2
[103]
PPO 3
[104]
PPO 4
[105]
PPO 5
[106]
PPO 6
[107]
PPO 7
[108]
PPO 8
[200]
Custom telegram 1
[202]
Custom telegram 3
8-41 Parameters for signals
Option:
[0] *
None
[302]
Minimum Reference
[303]
Maximum Reference
[312]
Catch up/slow Down Value
[341]
Ramp 1 Ramp up Time
[342]
Ramp 1 Ramp Down Time
[351]
Ramp 2 Ramp up Time
140
Function:
In a noisy environments, the interface may be blocked by due to overload of bad frames. This
parameter specifies the time between two consecutive frames on the network. If the interface does
not detect valid frames in that time it flushes the receive buffer.
Function:
Specify the minimum delay time between receiving a request and transmitting a response. This is
used for overcoming modem turnaround delays.
Function:
Specify the maximum permissible delay time between transmitting a request and receiving a re-
sponse. Exceeding this delay time will cause control word time-out.
Function:
Specify the maximum permissible time interval between receipt of two bytes. This parameter acti-
vates time-out if transmission is interrupted.
This parameter is active only when par. 8-30
Function:
Enables use of freely configurable telegrams or standard telegrams for the FC port.
Enables use of freely configurable telegrams or standard telegrams for the FC port.
Function:
This parameter contains a list of signals available for selection in par. 8-42
tion
PCD read configuration
and par. 8-43
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
FC 300 Programming Guide
Protocol
is set to
FC MC
[1] protocol.
PCD write configura-
.