FC 300 Programming Guide
9-67 Control Word 1
Range:
0*
[0 - 65535 ]
9-68 Status Word 1
Range:
0*
[0 - 65535 ]
9-70 Programming Set-up
Option:
[0]
Factory setup
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9] *
Active Set-up
This parameter is unique to LCP and fieldbuses. See also par. 0-11
9-71 Profibus Save Data Values
Option:
[0] *
Off
[1]
Store all setups
[2]
Store all setups
9-72 ProfibusDriveReset
Option:
[0] *
No action
[1]
Power-on reset
[3]
Comm option reset
9-75 DO Identification
Range:
0*
[0 - 65535 ]
Function:
This parameter accepts the Control Word from a Master Class 2 in the same format as PCD 1.
Function:
This parameter delivers the Status Word for a Master Class 2 in the same format as PCD 2.
Function:
Select the set-up to be edited.
Uses default data. This option can be used as a data source to return the other set-ups to a known
state.
Edits Set-up 1.
Edits Set-up 2.
Edits Set-up 3.
Edits Set-up 4.
Follows the active set-up selected in par. 0-10
Programming Set-up
Function:
Parameter values changed via Profibus are not automatically stored in non-volatile memory. Use
this parameter to activate a function that stores parameter values in the EEPROM non-volatile
memory, so changed parameter values will be retained at power-down.
Deactivates the non-volatile storage function.
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
Function:
Resets frequency converter upon power-up, as for power-cycle.
Resets the Profibus option only, useful after changing certain settings in parameter group 9-**, e.g.
par. 9-18
Node Address
.
When reset, the frequency converter disappears from the fieldbus, which may cause a communi-
cation error from the master.
Function:
Provides information about the DO (Drive Object).
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
3 Parameter descriptions
Active Set-up
.
.
3
159