3 Parameter descriptions
Par. 1-01
[0] U/f
plus
[1] VVC
[2] Flux sensorless
[3] Flux w/ motor feedback
3
Table 3.3: Overview of possible combinations of the settings in par. 1-00
the possible combinations.
1-02 Flux Motor Feedback Source
Option:
[0]
Motor feedb. P1-02
[1] *
24V encoder
[2]
MCB 102
[3]
MCB 103
[5]
MCO Encoder 2
[6]
Analog input 53
[7]
Analog input 54
[8]
Frequency input 29
[9]
Frequency input 33
This parameter cannot be adjusted while the motor is running.
1-03 Torque Characteristics
Option:
[0] *
Constant torque
[1]
Variable torque
[2]
Auto Energy Optim.
[5]
Constant Power
This parameter cannot be adjusted while the motor is running.
1-04 Overload Mode
Option:
[0] *
High torque
[1]
Normal torque
This parameter cannot be adjusted while the motor is running.
46
[0] Speed
[1] Speed
[2] Torque [3] Process [4] Torque
OL
CL
Function:
Select the interface at which to receive feedback from the motor.
A and B channel encoder, which can be connected to the digital input terminals 32/33 only. Termi-
nals 32/33 must be programmed to
Encoder module option which can be configured in par. group 17-1*
This parameter appears in FC 302 only.
Optional resolver interface module which can be configured in par. group 17-5**
encoder interface 2 of the optional programmable motion controller MCO 305.
Function:
Select the torque characteristic required.
VT and AEO are both energy saving operations.
Motor shaft output provides constant torque under variable speed control.
Motor shaft output provides variable torque under variable speed control. Set the variable torque
level in par. 14-40
Automatically optimises energy consumption by minimising magnetisation and frequency via
AEO Minimum Magnetisation
par. 14-41
The function provide a constant power in field weakening area. Follows the formula:
Torque x RPM
P constant
=
This selection maybe unavailable depending on drive configuration.
Function:
Allows up to 160% over torque.
For oversized motor - allows up to 110% over torque.
MG.33.M8.02 - VLT
Par. 1-00
[5] Wobble
OL
Configuration Mode
and par. 1-01
No operation
.
VT Level
.
and par. 14-42
9550
®
is a registered Danfoss trademark
FC 300 Programming Guide
[6] Surface
[7] Ext. PID
[8] Ext. PID
Wnd
OL
CL
Motor Control Principle
. The gray cells mark
Minimum AEO Frequency
.