• The DeviceNet Instruction Manual provides information on how to control, monitor, and In no event shall Danfoss be liable for direct, indirect, program the adjustable frequency drive via a special, incidental, or consequential damages arising out of DeviceNet serial communication bus.
Adjustable frequency drives do not fall under the machinery directive. However, if an adjustable frequency DISCHARGE TIME drive is supplied for use in a machine, Danfoss provides Adjustable frequency drives contain DC link capacitors information on safety aspects relating to the adjustable that can remain charged even when the adjustable frequency drive.
Page 18
As EMC directive either by using CE-labeled an aid to the installer, Danfoss has prepared EMC instal- components or by testing the EMC of the system. lation guidelines for the power drive system. If the EMC-...
All Danfoss adjustable frequency drives comply with the requirements for both the industrial and the home/office environment. To document immunity against electrical interference from electrical phenomena, the following immunity tests have been made on a system consisting of an adjustable frequency drive (with options, if relevant), a shielded control cable and a control box with potentiometer, motor cable, and motor.
3.6.1 PELV - Protective Extra Low Voltage WARNING Installation at high altitude: 380–500 V, enclosure D, E, and F: At altitudes above 10,000 ft [3 km], contact Danfoss regarding PELV. WARNING Figure 3.27 Galvanic Isolation Touching the electrical parts could be fatal - even after the equipment has been disconnected from line power.
Page 56
Table 3.18 Braking at High Overload Torque Level Danfoss offers brake resistors with duty cycle of 5%, 10% and 40%. If a 10% duty cycle is applied, the brake resistors are able to absorb braking energy for 10% of the cycle time. The remaining 90% of the cycle time is used on dissipating excess heat.
Page 57
Check that the brake resistor can handle a voltage of The brake is protected against short-circuiting of the brake 410 V, 820 V, 850 V, 975 V, or 1130 V - unless Danfoss resistor, and the brake transistor is monitored to ensure brake resistors are used.
To avoid the premature ageing of motors that are not designed to be used with adjustable frequency drives, such as those motors without phase insulation paper or other insulation reinforcement, Danfoss strongly recommends a dU/dt filter or a sine-wave filter fitted on the output of the adjustable frequency drive. For further information about dU/dt and sine-wave filters see the Output Filters Design Guide.
For the FC 300 series, order standard adjustable frequency Phases drives and adjustable frequency drives with integral AC Line Voltage options by sending a type code string describing the product to the local Danfoss sales office, for example: Enclosure 13-15 Enclosure type Enclosure class...
=Nominal resistance required to achieve 150% braking torque. br,nom =Resistance value of the recommended Danfoss brake resistor. Larger adjustable frequency drives include multiple inverter modules with a brake chopper in each inverter. Equal resistors should be connected to each brake chopper.
Page 99
=Nominal resistance required to achieve 150% braking torque. br,nom =Resistance value of the recommended Danfoss brake resistor. Larger adjustable frequency drives include multiple inverter modules with a brake chopper in each inverter. Equal resistors should be connected to each brake chopper.
Page 208
If one of the 6-pulse modular rectifiers becomes inoperable, it is possible to operate the adjustable frequency drive at reduced load with a single 6-pulse rectifier. Contact Danfoss for reconnection details. No paralleling of line power cabling is shown here. A 12-pulse adjustable frequency drive used as a 6-pulse should have line cables of equal numbers and lengths.
Danfoss recommends the fuses from the following tables. Selecting the proper fuses and circuit breakers minimizes damage due to an overcurrent condition within the adjustable frequency drive. If fuses/circuit breakers are chosen according to recommendations, possible damages are limited mainly to inside the unit.
Install a shaft grounding system or use an cations, use the motor insulation ratings shown in isolating coupling. Table 7.66. If a motor has lower insulation rating, Danfoss • Apply conductive lubrication. recommends using a dU/dt or sine wave filter.
When connecting the PC to the adjustable frequency drive conductive backplate on the adjustable frequency through a USB cable, Danfoss recommends using a USB drive and to the metal cabinet of the brake isolator with galvanic isolation to protect the PC USB host resistor.
Keep the ground wire connections as short as allowed but not recommended. See also possible. chapter 2.3.3 Danfoss Adjustable Frequency Drive and CE Connect the different ground systems at the lowest Labeling, chapter 3.5 General Aspects of EMC, possible conductor impedance. Obtain the lowest possible chapter 3.5.2 EMC Test Results, and chapter 7.8.3 Grounding...
80 ft [25 Figure 7.62. m], Danfoss recommends setting the 14-50 RFI 1 to [ON]. Refer also to the Application Note, VLT on IT Line Power, MN50P. It is important to use isolation monitors that are capable for use together with power electronics (IEC 61557-8).
Use the free Danfoss MCT 31 calculation software to determine the degree of voltage pollution on the grid and Example: If one of the motors is connected directly online ®...
Options and Accessories Design Guide 9 Options and Accessories 9.1.3 Slot C Danfoss offers a wide range of options and accessories for ® the VLT AutomationDrive. The power to the adjustable frequency drive must be 9.1.1 Slot A disconnected. For discharge time, see the instructions supplied with the option.
German NAMUR NE37 recommendations. ® The MCB 113 is a standard C1-option for the Danfoss VLT AutomationDrive and is detected automatically after mounting. For information on mounting and installing the option, see chapter 9.1.3 Slot C.
The resistor is selected in respect to its ohmic value, its power dissipation rate, and its physical size. Danfoss offers a wide variety of different resistors that are specially designed to our adjustable frequency drives. For the dimensioning of brake resistors, see chapter 3.8.3 Selection of Brake Resistor .
A terminal cover, supplied with the adjustable frequency drive, must be installed to maintain the IP20 For the FC 300, Danfoss can supply a sine-wave filter to rating of the enclosure. Figure 9.21 shows both the covered dampen the acoustic motor noise.
The FC protocol, also referred to as FC bus or Standard network at both ends. For this purpose, set switch S801 on bus, is the Danfoss standard serial communication bus. It the control card to "ON". For more information, see defines an access technique according to the master/ chapter 7.5.4 Switches S201 (A53), S202 (A54), and S801.
No responses are returned to broadcast queries from the master. The Modbus RTU Danfoss assumes that the installed controller supports the protocol establishes the format for the master query by interfaces in this manual, and strictly observes all...
Page 296
Danfoss shall not be responsible for any errors in catalogs, brochures or other printed material. Danfoss reserves the right to alter its products at any time without notice, provided that alterations to products already on order shall not require material changes in specifications previously agreed upon by Danfoss and the Purchaser. All trademarks in this material are property of the respective companies.