3 Parameter descriptions
20
mA
/
desired maximum current x
3
6-53 Terminal 42 Output Bus Control
Range:
0.00 %*
[0.00 - 100.00 %]
6-54 Terminal 42 Output Timeout Preset
Range:
0.00 %*
[0.00 - 100.00 %]
6-55 Terminal 42 Output Filter
Option:
[0] *
Off
[1]
On
3.8.8 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4 - 20 mA. Common terminal (terminal X30/8) is the same terminal and electrical potential for analog common
connection. Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Option:
122
value in the parameter, i.e. 50% = 20 mA. If a current between 4 and 20 mA is desired at maximum
output (100%), calculate the percentage value as follows:
100 %
Function:
Holds the level of Output 42 if controlled by bus.
Function:
Holds the preset level of Output 42.
In case of a bus timeout and a timeout function is selected in par. 6-50
output will preset to this level.
Function:
The following readout analogue parameters from selection in par. 6-50
filter selected when par. 6-55
Selection
Motor current (0 - I
)
max
Torque limit (0 - T
)
lim
Rated torque (0 - T
)
nom
Power (0 - P
)
nom
Speed (0 - Speedmax)
Filter off
Filter on
Function:
Select the function of Terminal X30/8 as an analog current output. Depending on the selection the
output is either a 0-20 mA or 4-20 mA output. The current value can be read out in LCP in
Analog Output 42 [mA]
par. 16-65
®
MG.33.M8.02 - VLT
20
i
e
mA
x
.
. 10
:
100 = 200 %
10
Terminal 42 Output Filter
is on:
0-20 mA 4-20 mA
[103]
[133]
[104]
[134]
[105]
[135]
[106]
[136]
[107]
[137]
.
is a registered Danfoss trademark
FC 300 Programming Guide
Terminal 42 Output