3 Parameter descriptions
3
1-21 Motor Power [HP]
Range:
Application
[Application dependant]
dependent*
1-22 Motor Voltage
Range:
Application
[Application dependant]
dependent*
1-23 Motor Frequency
Range:
Application
[20 - 1000 Hz]
dependent*
1-24 Motor Current
Range:
Application
[Application dependant]
dependent*
1-25 Motor Nominal Speed
Range:
Application
[10 - 60000 RPM]
dependent*
1-26 Motor Cont. Rated Torque
Range:
Application
[0.1 - 10000.0 Nm]
dependent*
1-29 Automatic Motor Adaptation (AMA)
Option:
48
This parameter cannot be adjusted while the motor is running. This parameter is visible in LCP if
Regional Settings
International
par. 0-03
is
NB!
Four sizes down, one size up from nominal unit rating.
Function:
Enter the nominal motor power in HP according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit. This parameter is visible in LCP if
par. 0-03
Regional Settings
is
US
[1]
Function:
Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
Function:
Min - Max motor frequency: 20 - 1000 Hz.
Select the motor frequency value from the motor nameplate data. If a value different from 50 Hz
or 60 Hz is selected, it is necessary to adapt the load independent settings in par. 1-50
Magnetisation at Zero Speed
to par. 1-53
V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
[RPM]
Maximum Reference
and par. 3-03
Function:
Enter the nominal motor current value from the motor nameplate data. The data are used for cal-
culating torque, motor protection etc.
Function:
Enter the nominal motor speed value from the motor nameplate data. The data are used for cal-
culating motor compensations.
NB!
Motor speed must always be lower than synchronous speed.
Function:
Enter the value from the motor nameplate data. The default value corresponds to the nominal rated
output. This parameter is available when par. 1-10
SPM
[1], i.e. the parameter is valid for PM and non-salient SPM motors only.
Function:
The AMA function optimises dynamic motor performance by automatically optimising the advanced
Stator Resistance (Rs)
motor parameters (par. 1-30
standstill.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
FC 300 Programming Guide
[0].
Model Shift Frequency
. For 87 Hz operation with 230/400
Motor Speed High Limit
to the 87 Hz application.
Motor Construction
is set to
Main Reactance (Xh)
to par. 1-35
Motor
PM, non salient
) at motor