Danfoss VLT AutomationDrive FC 300 Programming Manual page 36

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

FC 300 Programming Guide
NB!
Please refer to par. 0-37
texts.
0-20 Display Line 1.1 Small
Option:
[0]
None
[9]
Performance Monitor
[37]
Display Text 1
[38]
Display Text 2
[39]
Display Text 3
[953]
Profibus Warning Word
[1005]
Readout Transmit Error Counter
[1006]
Readout Receive Error Counter
[1007]
Readout Bus Off Counter
[1013]
Warning Parameter
[1230]
Warning Parameter
[1472]
VLT Alarm Word
[1473]
VLT Warning Word
[1474]
VLT Ext. Status Word
[1501]
Running Hours
[1502]
kWh Counter
[1600]
Control Word
[1601]
Reference [Unit]
[1602]
Reference %
[1603]
Status Word
[1605]
Main Actual Value [%]
[1609]
Custom Readout
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor Voltage
[1613]
Frequency
[1614]
Motor Current
[1615]
Frequency [%]
[1616]
Torque [Nm]
[1617] *
Speed [RPM]
[1618]
Motor Thermal
[1619]
KTY sensor temperature
[1620]
Motor Angle
[1621]
Torque [%] High Res.
[1622]
Torque [%]
Display Text 1
, par. 0-38
Display Text 2
Function:
Select a variable for display in line 1, left position.
No display value selected.
Present control word
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in selected
unit.
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in percent.
Present status word.
Actual value as a percentage.
Actual power consumed by the motor in kW.
Actual power consumed by the motor in HP.
Voltage supplied to the motor.
Motor frequency, i.e. the output frequency from the frequency converter in Hz
Phase current of the motor measured as effective value.
Motor frequency, i.e. the output frequency from the frequency converter in percent.
Actual motor torque in Nm
Speed in RPM (revolutions per minute) i.e. the motor shaft speed in closed loop.
Thermal load on the motor, calculated by the ETR function.
Present motor load as a percentage of the rated motor torque.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
and par. 0-39
Display Text 3
for information on how to write display
3 Parameter descriptions
3
35

Advertisement

Table of Contents
loading