FC 300 Programming Guide
35-26 Term. X48/7 Low Temp. Limit
Range:
Application
[Application dependant]
dependent*
35-27 Term. X48/7 High Temp. Limit
Range:
Application
[Application dependant]
dependent*
3.21.4 35-3* Temp. Input X48/10 (MCB 114)
35-34 Term. X48/10 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
35-35 Term. X48/10 Temp. Monitor
This parameter gives the possibility of enabling or disabling the temperature monitor for terminal X48/10. The temperature limits can be set in pars.
35-36/37.
Option:
[0] *
Disabled
[1]
Enabled
35-36 Term. X48/10 Low Temp. Limit
Range:
Application
[Application dependant]
dependent*
35-37 Term. X48/10 High Temp. Limit
Range:
Application
[Application dependant]
dependent*
3.21.5 35-4* Analog Input X48/2 (MCB 114)
35-42 Term. X48/2 Low Current
Range:
4.00 mA*
[Application dependant]
35-43 Term. X48/2 High Current
Range:
20.00 mA*
[Application dependant]
35-44 Term. X48/2 Low Ref./Feedb. Value
Range:
0.000*
[-999999.999 - 999999.999 ]
Function:
Enter the minimum temperature reading that is expected for normal operation of the temperature
sensor at terminal X48/7.
Function:
Enter the maximum temperature reading that is expected for normal operation of the temperature
sensor at terminal X48/7.
Function:
Enter the filter time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal X48/10. A high time constant value improves dampening but also in-
creases the time delay through the filter.
Function:
Function:
Enter the minimum temperature reading that is expected for normal operation of the temperature
sensor at terminal X48/10.
Function:
Enter the maximum temperature reading that is expected for normal operation of the temperature
sensor at terminal X48/10.
Function:
Enter the current (mA) that corresponds to the low reference value, set in par. 35-44. The value
must be set at > 2 mA in order to activate the Live Zero Time-out Function in par. 6-01.
Function:
Enter the current (mA) that corresponds to the high reference value (set in par. 35-45).
Function:
Enter the reference or feedback value (in RPM, Hz, bar, etc.) that corresponds to the voltage or
current set in par. 35-42.
®
MG.33.M8.02 - VLT