Danfoss VLT AutomationDrive FC 300 Programming Manual page 32

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

FC 300 Programming Guide
Russian
Thai
Bahasa Indonesia
[99]
Unknown
0-02 Motor Speed Unit
Option:
[0]
RPM
[1] *
Hz
0-03 Regional Settings
Option:
[0] *
International
[1]
US
This parameter cannot be adjusted while the motor is running.
0-04 Operating State at Power-up (Hand)
Option:
[0]
Resume
[1] *
Forced stop, ref=old
[2]
Forced stop, ref=0
3.2.3 0-1* Set-up Operations
Define and control the individual parameter setups.
The frequency converter has four parameter setups that can be programmed independently of each other. This makes the frequency converter very
flexible and able to solve advanced control functionality problems, often saving the cost of external control equipment. For example these can be used
to program the frequency converter to operate according to one control scheme in one setup (e.g. motor 1 for horizontal movement) and another control
scheme in another setup (e.g. motor 2 for vertical movement). Alternatively they can be used by an OEM machine builder to identically program all their
factory fitted frequency converters for different machine types within a range to have the same parameters and then during production/commissioning
simply select a specific setup depending on which machine the frequency converter is installed on.
Part of Language package 3
Part of Language package 2
Part of Language package 2
Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par. 0-02
Settings
. The default setting of par. 0-02
on which region of the world the frequency converter is supplied to, but can be re-programmed as
required.
NB!
Motor Speed Unit
Changing the
It is recommended to select the motor speed unit first, before modifying other
parameters.
Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in
terms of motor speed (RPM).
Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in
terms of output frequency to the motor (Hz).
Function:
Activates par. 1-20
Motor Power [kW]
Motor Frequency
of par. 1-23
to 50 Hz.
Motor Power [kW]
Activates par. 1-20
Motor Frequency
of par. 1-23
to 60 Hz.
Function:
Selects the operating mode upon reconnection of the frequency converter to mains voltage after
power down in Hand (local) operation mode.
Restarts the frequency converter maintaining the same local reference and the same start/stop
settings (applied by [HAND ON/OFF]) as before the frequency converter was powered down.
Restarts the frequency converter with a saved local reference, after mains voltage reappears and
after pressing [HAND ON].
Resets the local reference to 0 upon restarting the frequency converter.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
3 Parameter descriptions
Motor Speed Unit
Motor Speed Unit
Regional Settings
and par. 0-03
will reset certain parameters to their initial value.
for setting the motor power in kW and sets the default value
for setting the motor power in HP and sets the default value
3
Regional
and par. 0-03
depends
31