3 Parameter descriptions
3-18 Relative Scaling Reference Resource
Option:
3
[0] *
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Frequency input 29
[8]
Frequency input 33
[11]
Local bus reference
[20]
Digital pot.meter
[21]
Analog input X30-11
[22]
Analog input X30-12
3-19 Jog Speed [RPM]
Range:
Application
[Application dependant]
dependent*
3.5.4 Ramps
3-4* Ramp 1
For each of four ramps (par. 3-4*, par. 3-5*, par. 3-6* and par. 3-7*) configure the ramp parameters: ramp type, ramping times (duration of acceleration
and deceleration) and level of jerk compensation for S ramps.
Start by setting the linear ramping times corresponding to the figures.
76
Function:
Select a variable value to be added to the fixed value (defined in par. 3-14
ence
). The sum of the fixed and variable values (labelled Y in the illustration below) is multiplied
with the actual reference (labelled X in the illustration below). This product is then added to the
actual reference (X+X*Y/100) to give the resultant actual reference.
This parameter cannot be adjusted while the motor is running.
Function:
Enter a value for the jog speed n
, which is a fixed output speed. The frequency converter runs
JOG
at this speed when the jog function is activated. The maximum limit is defined in par. 4-13
Speed High Limit [RPM]
.
See also par. 3-80
Jog Ramp Time
.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
FC 300 Programming Guide