[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[119]
Torque % lim
5-68 Pulse Output Max Freq #X30/6
Select the maximum frequency on terminal X30/6 referring to the output variable in par. 5-66
cannot be adjusted while the motor is running.
This parameter is active when option module MCB 101 is mounted in the frequency converter.
Range:
Application
[0 - 32000 Hz]
dependent*
3.7.8 5-7* 24 V Encoder Input
Parameters for configuring the 24 V encoder.
Connect the 24 V encoder to terminal 12 (24 V DC supply), terminal 32 (Channel A), terminal 33 (Channel B), and terminal 20 (GND). The digital inputs
32/33 are active for encoder inputs when
The encoder used is a dual channel (A and B) 24 V type. Max input frequency: 110 kHz.
Encoder Connection to the frequency converter
24 V incremental encoder. Max. cable length 5 m.
5-70 Term 32/33 Pulses per Revolution
Range:
1024*
[1 - 4096 ]
Function:
24 V encoder
is selected in par. 1-02
Function:
Set the encoder pulses per revolution on the motor shaft. Read the correct value from the encoder.
This parameter cannot be adjusted while the motor is running.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
Terminal X30/6 Pulse Output Variable
Flux Motor Feedback Source
and par. 7-00
3 Parameter descriptions
3
. This parameter
Speed PID Feedback Source
.