14-24 Trip Delay at Current Limit
Range:
60 s*
[0 - 60 s]
14-25 Trip Delay at Torque Limit
Range:
60 s*
[0 - 60 s]
200
Initialization
Select
[2] to reset all parameter values to default settings, except for par. 15-03
Up's
Over Temp's
, par. 15-04
, and par. 15-05
the next power-up.
Par. 14-22
Operation Mode
will also revert to the default setting
Function:
Enter the current limit trip delay in seconds. When the output current reaches the current limit
Current Limit
(par. 4-18
), a warning is triggered. When the current limit warning has been contin-
uously present for the period specified in this parameter, the frequency converter trips. Disable the
trip delay by setting the parameter to 60 s = OFF. Thermal monitoring of the frequency converter
will still remain active.
Function:
Enter the torque limit trip delay in seconds. When the output torque reaches the torque limits
Torque Limit Motor Mode
(par. 4-16
triggered. When the torque limit warning has been continuously present for the period specified in
this parameter, the frequency converter trips. Disable the trip delay by setting the parameter to 60
s = OFF. Thermal monitoring of the frequency converter will still remain active.
®