Danfoss VLT AutomationDrive FC 300 Programming Manual page 79

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

3 Parameter descriptions
3-42 Ramp 1 Ramp Down Time
Range:
Application
[Application dependant]
dependent*
3
3-45 Ramp 1 S-ramp Ratio at Accel. Start
Range:
50 %*
[Application dependant]
3-46 Ramp 1 S-ramp Ratio at Accel. End
Range:
50 %*
[Application dependant]
3-47 Ramp 1 S-ramp Ratio at Decel. Start
Range:
50 %*
[Application dependant]
3-48 Ramp 1 S-ramp Ratio at Decel. End
Range:
50 %*
[Application dependant]
3.5.5 3-5* Ramp 2
Choosing ramp parameters, see 3-4*.
3-50 Ramp 2 Type
Option:
[0] *
Linear
[1]
S-ramp Const Jerk
[2]
S-ramp Const Time
NB!
If S-ramp [1] is selected and the reference during ramping is changed the ramp time may be prolonged in order to realize a jerk free
movement which may result in a longer start or stop time.
Additional adjustment of the S-ramp ratios or switching initiators may be necessary.
78
Function:
Enter the ramp-down time, i.e. the deceleration time from the synchronous motor speed n
RPM. Choose a ramp-down time such that no over-voltage arises in the inverter due to regenerative
operation of the motor, and such that the generated current does not exceed the current limit set
Current Limit
in par. 4-18
. The value 0.00 corresponds to 0.01 s in speed mode. See ramp-up time
Ramp 1 Ramp up Time
in par. 3-41
.
t dec s x n s RPM
Par
. 3 − 42 =
ref RPM
Function:
Enter the proportion of the total ramp-up time (par. 3-41
acceleration torque increases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks occurring in the application.
Function:
Enter the proportion of the total ramp-up time (par. 3-41
acceleration torque decreases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks in the application.
Function:
Enter the proportion of the total ramp-down time (par. 3-42
deceleration torque increases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks in the application.
Function:
Enter the proportion of the total ramp-down time (par. 3-42
deceleration torque decreases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks in the application.
Function:
Select the ramp type, depending on requirements for acceleration/deceleration. A linear ramp will
give constant acceleration during ramping. An S-ramp will give non-linear acceleration, compen-
sating for jerk in the application.
Acceleration with lowest possible jerk
S-ramp based on the values set in par. 3-51
down Time
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
FC 300 Programming Guide
Ramp 1 Ramp up Time
Ramp 1 Ramp up Time
Ramp 1 Ramp Down Time
Ramp 1 Ramp Down Time
Ramp 2 Ramp up Time
and par. 3-52
to 0
s
) in which the
) in which the
) where the
) where the
Ramp 2 Ramp

Advertisement

Table of Contents
loading

Table of Contents