FC 300 Programming Guide
1-05 Local Mode Configuration
Option:
[0]
Speed open loop
[1]
Speed closed loop
[2] *
As mode par 1-00
1-06 Clockwise Direction
This parameter defines the term "Clockwise" corresponding to the LCP direction arrow. Used for easy change of direction of shaft rotation without
swapping motor wires. (Valid from SW version 5.84)
Option:
[0] *
Normal
[1]
Inverse
This parameter cannot be changed while the motor is running.
3.3.2 1-1* Motor Selection
Parameter group for setting general motor data.
This parameter group cannot be adjusted while the motor is running.
1-10 Motor Construction
Option:
[0] *
Asynchron
[1]
PM, non salient SPM
Motor construction can either be asynchronous or permanent magnet (PM) motor.
3.3.3 1-2* Motor Data
Parameter group 1-2* comprises input data from the nameplate on the connected motor.
Parameters in parameter group 1-2* cannot be adjusted while the motor is running.
NB!
Changing the value of these parameters affects the setting of other parameters.
1-20 Motor Power [kW]
Range:
Application
[Application dependant]
dependent*
Function:
Select which application configuration mode (par. 1-00
principle, to use when a Local (LCP) Reference is active. A Local Reference can be active only when
Reference Site
par. 3-13
is set to [0] or [2]. By default the local reference is active in Hand Mode
only.
Function:
Motor shaft will turn in clockwise direction when frequency converter is connected U -> U; V -> V,
and W -> W to motor.
Motor shaft will turn in counter clockwise direction when frequency converter is connected U -> U;
V -> V, and W -> W to motor.
Function:
Select the motor construction type.
For asynchronous motors.
For permanent magnet (PM) motors.
Note that PM motors are divided into two groups, with either surface mounted (non salient) or
interior (salient) magnets.
Function:
Enter the nominal motor power in kW according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
3 Parameter descriptions
Configuration Mode
), i.e. application control
3