FC 300 Programming Guide
5-42 Off Delay, Relay
Array [9] (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
0.01 s*
[0.01 - 600.00 s]
If the selected Event condition changes before the on- or off delay timer expires, the relay output is unaffected.
3.7.6 5-5* Pulse Input
The pulse input parameters are used to define an appropriate window for the impulse reference area by configuring the scaling and filter settings for the
pulse inputs. Input terminals 29 or 33 act as frequency reference inputs. Set terminal 29 (par. 5-13
Terminal 33 Digital Input
(par. 5-15
5-50 Term. 29 Low Frequency
Range:
100 Hz*
[0 - 110000 Hz]
5-51 Term. 29 High Frequency
Range:
100 Hz*
[0 - 110000 Hz]
5-52 Term. 29 Low Ref./Feedb. Value
Range:
0.000 Ref-
[-999999.999 - 999999.999 Refer-
erenceFeed-
enceFeedbackUnit]
backUnit*
Function:
Enter the delay of the relay cut-out time. Select one of available mechanical relays and MCB 105 in
an array function. See par. 5-40
Pulse input
) to
[32]. If terminal 29 is used as an input, then set par. 5-01
Function:
Enter the low frequency limit corresponding to the low motor shaft speed (i.e. low reference value)
Term. 29 Low Ref./Feedb. Value
in par. 5-52
This parameter is available for FC 302 only.
Function:
Enter the high frequency limit corresponding to the high motor shaft speed (i.e. high reference
Term. 29 High Ref./Feedb. Value
value) in par. 5-53
This parameter is available for FC 302 only.
Function:
Enter the low reference value limit for the motor shaft speed [RPM]. This is also the lowest feedback
value, see also par. 5-57
®
MG.33.M8.02 - VLT
is a registered Danfoss trademark
Function Relay
.
Terminal 29 Digital Input
Terminal 27 Mode
. Refer to the diagram in this section.
.
Term. 33 Low Ref./Feedb. Value
. Set terminal 29 to digital input
3 Parameter descriptions
3
) or terminal 33
Input
to
[0].
109