1.4 Approvals and Certifications Illustration 1: Approvals and Certifications More approvals and certifications are available. Contact the local Danfoss office or partner. Drives of voltage T7 (525–690 V) are UL certified for only 525–600 V. Thermal memory retention requirement The drive complies with UL 61800-5-1 thermal memory retention requirements. For more information, refer to the Motor Thermal Protection section in the product-specific design guide.
Page 39
There is a risk for overvoltage. Isolation between components and critical parts could be insufficient, and may not comply with PELV requirements. Use external protective devices or galvanic isolation. For installations above 2000 m (6500 ft) altitude, contact Danfoss regarding PELV compliance.
Page 45
Operating Guide | VLT® AQUA Drive FC 202 N O T I C E OUTPUT CONTACTOR Danfoss does not recommend using an output contactor on 525-690 V drives that are connected to an IT mains network. Procedure 1. Strip a section of the outer cable insulation.
RS485 is a 2-wire bus interface compatible with multi-drop network topology. This interface contains the following features: • Either Danfoss FC or Modbus RTU communication protocol can be used. • Functions can be programmed remotely using the protocol software and RS485 connection or in parameter group 8-** Communications and Options.
7.1.12 Wiring Configuration for a Submersible Pump ® The system consists of a submersible pump controlled by a Danfoss VLT AQUA Drive and a pressure transmitter. The transmitter gives a 4–20 mA feedback signal to the drive, which keeps a constant pressure by controlling the speed of the pump. To design a drive for a submersible pump application, there are a few important issues to consider.
Page 94
• It is important that the system is operated with a minimum of wear and tear on the pump and motor. A Danfoss sine-wave filter can lower the motor insulation stress and increase lifetime (check actual motor insulation and the drive dU/dt specification). Most manufacturers of submersible pumps require the use of output filters.
Page 110
8.4.14 ALARM 15, Hardware Mismatch Cause A fitted option is not operational with the present control card hardware or software. Troubleshooting Record the value of the following parameters and contact Danfoss. • Parameter 15-40 FC Type. • Parameter 15-41 Power Section.
Page 115
Check that the option is properly installed. • Check for loose or missing wiring. It may be necessary to contact the Danfoss supplier or service department. Note the code number for further troubleshooting directions. Table 43: Internal Fault Codes Number Text The serial port cannot be initialized.
Page 116
Operating Guide | VLT® AQUA Drive FC 202 Troubleshooting Number Text 1024-1284 Internal fault. Contact the Danfoss supplier or Danfoss service department. 1299 The option software in slot A is too old. 1300 The option software in slot B is too old.
Page 119
8.4.46 ALARM 50, AMA Calibration Failed Troubleshooting • Contact the Danfoss supplier or service department. 8.4.47 ALARM 51, AMA Check Unom and Inom Cause The settings for motor voltage, motor current, and motor power are wrong.
Page 133
(IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
(IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
Page 135
(IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
(IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
Page 174
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.