Installing Gsdml; Connecting The Converter To Ethernet/Ip - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

4.13.6

Installing GSDML

Procedure
1. Save the GSDML to your PC.
– With Internet access:
– Without Internet access:
2. Unzip the GSDML file on your computer.
3. Import the GSDML into the engineering system of the controller.
You have now installed the GSDML in the engineering system of the controller.
4.13.7

Connecting the converter to Ethernet/IP

Overview
To connect the converter to a control system via Ethernet, proceed as follows:
Procedure
1. Connect the converter to the control system via an Ethernet cable.
2. Create an object for data exchange.
You have the following options:
– Load the EDS file into your controller if you want to use the ODVA profile.
– If your controller does not accept the EDS file, or if you wish to use the SINAMICS
You have connected the converter to the control system via Ethernet/IP.
Example
You can find an example showing how to connect a converter to the control system via
Ethernet/IP on the Internet:
Application example (https://support.industry.siemens.com/cs/ww/en/view/82843076)
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
GSDML (https://support.industry.siemens.com/cs/ww/en/view/26641490)
Insert a memory card into the converter.
Set p0804 = 12.
The converter writes the GSDML as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
You can find the EDS file on the Internet:
EDS (https://support.industry.siemens.com/cs/ww/en/view/78026217)
profile, you must create a generic module in your controller:
Creating generic I/O module (Page 142)
4.13 Connecting to PROFINET and Ethernet
Wiring
79