Advertisement

Function description
Procedure
1. Select the button for the feedback signal.
2. Select the signal that matches your particular application.
You have interconnected the "STO active" checkback signal.
After STO has been selected, the converter signals "STO active" to the higher-level control.
Parameters
Parameter
r9773.0...31
7.15.2.5

Setting the filter for fail-safe digital inputs

Overview
The following filters are available for the fail-safe digital inputs:
• A filter for the simultaneity monitoring
• A filter for suppressing short signals, e.g. test pulses.
Function description
Discrepancy time for the simultaneity monitoring
The converter checks that the two input signals of the fail-safe digital input always have the
same signal state (high or low).
With electromechanical sensors (e.g. emergency stop buttons or door switches), the two
sensor contacts never switch at exactly the same time and are therefore temporarily
inconsistent (discrepancy). A permanent discrepancy signifies a fault in the fail-safe digital
input circuit, e.g. wire breakage.
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
The screen form varies depending on the interface selected.
(A)
Control type
Description
CO/BO: SI status (processor 1 + pro‐
cessor 2)
Advanced commissioning
7.15 Safe Torque Off (STO) safety function
Setting
Display and BICO output for the Safety Integrated
status on the drive (processor 1 + processor 2).
Bit 0: STO is selected in the drive
Bit 1: STO is active in the drive
Bit 31: Test stop is required for STO
239