1 OVERVIEW

1.6.3 Setting I/O No.

The procedure for the I/O No. setting of the Motion CPU in system settings of SW6RN-
GSV43P is shown below. In the Motion CPU, by setting a module used in each CPU
base or extension base slot in system settings, the control CPU of the applicable slot is
assigned as the self CPU. Input modules, output modules and composite I/O modules
require an I/O No. to be set.
Refer to the help of SW6RN-GSV43P for the detailed operating procedure on the
system settings screen.
<System Settings>
<Motion Slot Settings>
<I/O Module Settings>
POINT
I/O No.s cannot be assigned automatically, unlike a PLC CPU for which I/O No. are
assigned automatically if such setting is omitted in the Motion CPU. In the Motion
CPU, be sure to set the first I/O No. in System Settings for each module used.
1) Double-click the slot position, display
2) Select the I/O module.
3) Click [Detail Setting].
4) Select applicable module type
5) Set the first I/O No.
6) Click [OK].
1 - 54
the Motion Slot Settings dialog box.
and number of points for
the I/O module to be used.
(PX No., PY No.).