Communication speed setting

Set the communication speed.
Item
Communication Speed
*1 This speed can be used for the firmware version "04" or later.
For details on the connection of modules or devices based on the communication speed setting, refer to the following.
 MELSEC iQ-R CC-Link IE TSN User's Manual (Startup)

Supplementary Cyclic Settings

Set the station-based block data assurance and I/O maintenance settings.
Item
Station-based Block Data Assurance
I/O Maintenance
Settings

Transient Transmission Group No. Setting

Set the transient transmission group number.
Item
Transient Transmission Group No.
Setting

Communication Mode

Set the communication mode.
Item
Communication Mode
*1 This communication mode can be used for the firmware version "04" or later.

Parameter Name

Set a name for the module parameter if desired.
Item
Parameter Name
2 PARAMETER SETTINGS
110
2.4 Application Settings
Description
Select the communication speed.
Output Hold/Clear Setting during
CPU STOP
Data Link Error Station Setting
Output Mode upon CPU Error
Description
Set the group number to perform transient transmission using group specification.
Description
Set the communication mode.
Description
Set a name for the module parameter if desired.
Description
Select whether to ensure a data integrity of the data blocks being
refreshed between the CPU module and the RJ71GN11-T2. (
Page 35 Cyclic data assurance)
Select whether to hold or clear output when the status of the CPU
module changes from RUN to STOP. Set it on the sending side.
( Page 44 I/O maintenance settings)
Select whether to clear or hold input from a disconnected station.
Set it on the receiving side. ( Page 44 I/O maintenance
settings)
Select whether to hold or clear output when a stop error occurs in
the CPU module. Set it on the sending side. ( Page 44 I/O
maintenance settings)
Setting range
• 1Gbps
*1
• 100Mbps
(Default: 1Gbps)
Setting range
• Enable
• Disable
(Default: Enable)
• Hold
• Clear
(Default: Hold)
• Clear
• Hold
(Default: Clear)
• Clear
• Hold
(Default: Clear)
Setting range
0 to 32 (0: No group
specification)
(Default: 0)
Setting range
• Unicast
*1
• Multicast
(Default: Unicast)
Setting range
Up to 8 one-byte or two-byte
characters
(Default: empty)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn

Table of Contents