Station No./IP address setting

Set the station number and IP address of the own station of the FX5-CCLGN-MS.
Item
Description
Station No./IP Address
Select whether to set the station number using the engineering tool or set the station number/IP
Setting Method
address using a program (G(P).UINI instruction). This item can be set only for a local station.
When selecting "Program", use the G(P).UINI instruction to set the station number/IP address.
( MELSEC iQ-F FX5 Programming Manual (Instructions, Standard Functions/Function
Blocks))
Station No.
Set the station number of the FX5-CCLGN-MS. This item can be set only for a local station.
To set the station number in this setting, set "Station No./IP Address Setting Method" to
"Parameter Editor".
Set a station number different from those used in the same network.
IP Address
Set the IP address of the own station.
Set an IP address different from those used in other stations. ( Page 61 IP address
duplication detection)
Do not set the following values.
• The third and fourth octets are all 0 or all 1.
• The host address bits are all 0 or all 1.
• Reserved address
Subnet Mask
Set the subnet mask.
Set the same value for the master station and slave station.
If the subnet mask is empty, the address class (class A, class B, class C) is determined from the
setting of "IP Address", and operation is done with the subnet mask according to the address
class.
The subnet mask for each class is as follows.
• Class A: 255.0.0.0
• Class B: 255.255.0.0
• Class C: 255.255.255.0
The IP address for each class is as follows.
• Class A: 0.x.x.x to 127.x.x.x
• Class B: 128.x.x.x to 191.x.x.x
• Class C: 192.x.x.x to 223.x.x.x
The host address for each class is the 0 section shown below.
• Class A: 255.0.0.0
• Class B: 255.255.0.0
• Class C: 255.255.255.0
Default Gateway
Set the default gateway.
Setting range
• Parameter Editor
• Program
(Default: Parameter Editor)
• Master station: Fixed to "0"
• Local station: 1 to 120
(Default: 1)
0.0.0.1 to 223.255.255.254
(00.00.00.01 to DF.FF.FF.FE)
(Default: Master station
192.168.3.249, local station
192.168.3.11)
• Empty
• 0.0.0.1 to 255.255.255.255
(00.00.00.01 to FF.FF.FF.FF)
(Default: empty)
• Empty
• 0.0.0.1 to 223.255.255.254
(00.00.00.01 to DF.FF.FF.FE)
(Default: empty)