Machine data
3.2 General machine data
12030
OVR_FACTOR_FEEDRATE
-
Evaluation of path feedrate override switch
-
-
31
Description:
Evaluation of the feedrate override switch with gray-coded interface.
Special function of the 31st value for the velocity control:
The setting of the 31st override value defines the dynamic reserves which take the
velocity control to be an excessive increase in the path feed. The setting should
correspond to the highest override factor actually used.
Not relevant with:
MD12020 $MN_OVR_FEED_IS_GRAY_CODE = 0
Related to:
NC/PLC interface signal DB380x DBX0 (Feed override A-H)
12040
OVR_RAPID_IS_GRAY_CODE
-
Rapid traverse override switch Gray-coded
-
-
-
Description:
This machine data is used to adapt the rapid traverse override switch to the interface
coding of the PLC interface.
1:
override A-H) are interpreted as a Gray code. The value which is read corresponds to
a switch setting.
It is used as an index for selecting the correct override factor from the table of
MD12050 $MN_OVR_FACTOR_RAPID_TRA[n].
0:
representation of the override value in percent (limit 200 percent).
Related to:
NC/PLC interface signal DB3200 DBX5 (Rapid traverse override A-H)
MD12050 $MN_OVR_FACTOR_RAPID_TRA[n]
(Evaluation of the rapid traverse override switch)
12050
OVR_FACTOR_RAPID_TRA
-
Evaluation of rapid traverse override switch
-
-
31
Description:
Evaluation of the rapid traverse override switch with gray-coded interface.
Not relevant with:
MD12040 $MN_OVR_RAPID_IS_GRAY_CODE = 0
Related to:
NC/PLC interface signal DB3200 DBX5 (Rapid traverse override A-H)
12060
OVR_SPIND_IS_GRAY_CODE
-
Spindle override switch Gray-coded
-
-
-
Description:
This machine data is used to adapt the spindle speed override switch to the interface
coding of the PLC interface.
78
0.00, 0.01, 0.02, 0.04,
0.06, 0.08, 0.10, 0.20...
TRUE
The 5 low-order bits of the PLC interface signal DB3200 DBX5 (Rapid traverse
The rapid traverse override byte of the PLC interface is interpreted as a binary
0.00, 0.01, 0.02, 0.04,
0.06, 0.08, 0.10, 0.20...
TRUE
EXP, N10
DOUBLE
0.00
2.00
EXP, N10
BOOLEAN
0
-
EXP, N10
DOUBLE
0.00
1.00
EXP, N10
BOOLEAN
0
-
V1, B1, Z1
PowerOn
1/1
M
V1, Z1
PowerOn
1/1
M
V1, Z1
PowerOn
1/1
M
V1, Z1
PowerOn
1/1
M
Parameter Manual