Dx2010 Status Led; Dx2010 Supervision; Off-Board Outputs (Dx3010); Overview - Bosch DS7200V2-UK Installer's Manual

Table of Contents

Advertisement

Set the address DIP switches as shown in Table 8.
Shaded cells only apply to the DS7240V2.
DX2010 DIP Switch Settings
DIP
S1
S2
Switches
Data Bus
32
16
Address
101
OFF
OFF
102
OFF
OFF
103
OFF
OFF
104
OFF
OFF
105
OFF
OFF
106
OFF
OFF
107
OFF
OFF

Table 8: DX2010 DIP Switch Settings

See Figure 27 for proper DX2010 DIP switch
configuration.
ON
Example:
Module Address 102
1
2
3

Figure 27: DX2010 DIP Switch Configuration

18.8

DX2010 Status LED

• One flash per second indicates normal operation.
• LED steady ON can indicate any of the following:
− "G" wire is not connected or there is a
communications problem between the control
panel and the DX2010.
− No locations (zones) are assigned to the DX2010
with this address. See Locations on page 72 for
details.
− DX2010 address is not set correctly.
• LED OFF indicates that there is no power to the
module.
Status LED
ON
1
2

Figure 28: DX2010 Status LED Location

18.9

DX2010 Supervision

The control panel supervises proper communication
to the DX2010. If it fails to communicate with the
DX2010, it sends a "Dbus Missing" {125} report.
Page 22
P/N: 4998152533-02
PART II: SYSTEM INSTALLATION AND SETUP
S3
S4
S5
8
4
2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
4
5
6
DIP switches
3
4
5
6
Copyright  2007 Bosch Security Systems, Inc.
19.0

Off-board Outputs (DX3010)

19.1

Overview

S6
The DX3010 Output Expander allows you to add
outputs to your system in groups of eight.
1
The DS7240V2 supports up to 20 programmable
outputs (4 on-board, 16 off-board via 2 DX3010
OFF
Output Expanders).
ON
The DS7220V2 supports up to 12 programmable
OFF
utputs (4 on-board, 8 off-board via 1 DX3010
ON
Output Expander).
OFF
You can assign any of the programmable output
ON
functions to the DX3010's individual outputs
separately. See Outputs on page 86 for
OFF
programming details.
• DX3013 Output Expander: An Octo-Output
Expander mounted on an angle bracket for
installation inside the CX1011 Enclosure.
• Current Draw: 10 mA Standby plus 40 mA for
ON
each energized output (relay) for a total of 330 mA
maximum with all eight outputs energized.
Refer to the DX3010 Installation Guide (P/N: 49529)
for complete installation, addressing and operating
instructions.
19.2

DX3010 Configuration

19.3

DX3010 Relay Outputs

Each DX3010 output provides a Form "C" dry contact
rated for 5.0 A at 28 VDC. Normally Open, Common,
and Normally Closed terminals are available for each
relay output. When an individual output is activated,
there is continuity between the Normally Open and
Common terminals. When the output is not activated,
there is continuity between the Normally Closed and
Common terminals.
Outputs might activate when setting the
DX3010's address DIP switches,
programming the control panel, resetting
the control panel, or applying power to the
control panel. Disconnect equipment
connected to outputs when performing
these functions.
The DX3010 relay outputs are not
supervised and cannot be used in fire or
combined fire/burglary installations for
primary indicating devices.
DS7200V2-UK Installer's Guide

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ds7220v2Ds7240v2