Connection For External Auxiliary Equipment (Option L19) - Siemens SINAMICS G150 Operating Manual

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical Installation
4.9.2

Connection for External Auxiliary Equipment (Option L19)

Description
This option includes a connection fused at max. 10 A for external auxiliary
equipment (for example, separately driven fan for motor). The voltage is tapped at
the converter input and, therefore, has the same level as the supply voltage. The
connection can be controlled internally or externally.
Connection
Table 4-17
Terminal
1
2
3
11
12
13
14
15
16
PE
Max. connectable cross-section: 4 mm² (AWG 10)
Circuit Proposal for Controlling the Auxiliary Contactor from Within the
Converter
The following circuit, for example, can be used if the auxiliary contactor is to be
controlled from within the converter. The "Operation" message is then no longer
available for other purposes.
4-26
Terminal block X155 – connection for external auxiliary equipment
Designation
L1
L2
L3
Contactor control
Checkback from
circuit-breaker
Checkback from
contactor
PE
Technical data
3 AC 380 – 480 V
3 AC 660 -690 V
230 V AC
230 V AC / 0.5 A
24 V DC / 2 A
240 V AC / 6 A
PE
SINAMICS G150
Operating Manual
11/03

Advertisement

Table of Contents
loading

Table of Contents