Network No.

Set the network number of the Motion module.
Item
Description
Network No.
Set the network number of the Motion module.
Precautions
Set a network number that does not duplicate any other network numbers.
When a network number is duplicated in the same system, an error will occur in the CPU module.
In particular, when using an Ethernet-equipped module (CPU module) at default, the IP address is 192.168.3.250 and the
network number is the third octet of the IP address, thus 3. Because setting the network number of the Motion module to 3
causes duplication, set another network number.

Parameter Setting Method

Set "Basic Settings" and "Application Settings" items using the engineering tool or in program.
Item
Description
Setting Method of Basic/
Select this item to set the parameter using the engineering tool.
Application Settings
The following are advantages.
• All parameters can be easily set in the window without creating a program for setting.
• Data can be automatically transferred from the link special relay (SB), link special register
(SW), and link devices of the Motion module to the devices of the CPU module.

Station No./IP Address Setting

Set the station number and IP address of the own station of the Motion module.
Item
Description
Station No.
The master station is fixed to "0".
IP Address
Set the IP address of the own station.
Set an IP address different from those used in other stations. (Page 49 IP address
duplication detection)
Do not set the following values.
• The third and fourth octets are all 0 or all 1.
• The host address bits are all 0 or all 1.
• Reserved address
Subnet Mask
Set the subnet mask.
Set the same value for the master station and device station.
If the subnet mask is empty, the address class (class A, class B, class C) is determined from the
setting of "IP Address", and operation is done with the subnet mask according to the address
class.
The subnet mask for each class is as follows.
• Class A: 255.0.0.0
• Class B: 255.255.0.0
• Class C: 255.255.255.0
The IP address for each class is as follows.
• Class A: 0.x.x.x to 127.x.x.x
• Class B: 128.x.x.x to 191.x.x.x
• Class C: 192.x.x.x to 223.x.x.x
The host address for each class is the 0 section shown below.
• Class A: 255.0.0.0
• Class B: 255.255.0.0
• Class C: 255.255.255.0
Default Gateway
Set the default gateway.
Setting range
1 to 239
(Default: 1)
Setting range
Parameter Editor (fixed)
Setting range
0.0.0.1 to 223.255.255.254
(00.00.00.01 to DF.FF.FF.FE)
(Default: 192.168.3.249)
• Empty
• 0.0.0.1 to 255.255.255.255
(00.00.00.01 to FF.FF.FF.FF)
(Default: empty)
• Empty
• 0.0.0.1 to 223.255.255.254
(00.00.00.01 to DF.FF.FF.FE)
(Default: empty)