Parameter Setting Method - Mitsubishi Electric MELSEC iQ-R Series User Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Parameter Setting Method

Select whether to set "Basic Settings" and "Application Settings" items using the engineering tool or in program.
Item
Description
Setting Method of Basic/
■Parameter Editor
Application Settings
Select this item to set the parameter using the engineering tool.
The following are advantages.
• All parameters can be easily set in the window without creating a program for setting.
• The data will be automatically transferred from the link special relay (SB), link special register
(SW), and link devices of the RJ71GN11-T2 to the devices of the CPU module, the link special
relay (SB), link special register (SW) of the RJ71GN11-T2, and the module label of the CPU
module.
■Program
Select this item to set the parameter using the dedicated instructions (UINI instruction and
CCPASETX instruction), or the dedicated instructions (UINI instruction and CCPASET
instruction).
• Only "Required Settings" parameters can be set using the engineering tool.
• Also set "Station No./IP Address Setting Method" in "Required Settings" to "Program".
The following are advantages.
• Comparing with the number of modules that can be set in the engineering tool, larger
numbers of the RJ71GN11-T2s can be actually mounted. ( MELSEC iQ-R Module
Configuration Manual)
*1 When "Program" is selected, some parameters cannot be set using a dedicated instruction (CCPASET instruction).
For parameters that can be set using a dedicated instruction (CCPASET instruction), refer to the following.
 MELSEC iQ-R Programming Manual (Module Dedicated Instructions)
Station number/IP address setting of a local station
The station number/IP address of a local station can be also set using the UINI instruction. This allows project data items
other than the station number/IP address to be shared. ( MELSEC iQ-R Programming Manual (Module Dedicated
Instructions))
■When using the engineering tool for the parameter setting
The procedure for setting the station number of a local station is shown below.
1.
Set "Station No./IP Address Setting Method" under "Station No./IP Address Setting" in "Required Settings" to "Program".
2.
Set "Setting Method of Basic/Application Settings" under "Parameter Setting Method" in "Required Settings" to
"Parameter Editor".
3.
Set the station number/IP address using the UINI instruction.
■When using the CCPASETX instruction or CCPASET instruction for the parameter setting
The procedure for setting the station number of a local station is shown below.
1.
Set "Station Type" and "Network No." in "Required Settings".
2.
Set "Station No./IP Address Setting Method" under "Station No./IP Address Setting" in "Required Settings" to "Program".
3.
Set "Setting Method of Basic/Application Settings" under "Parameter Setting Method" in "Required Settings" to
"Program".
4.
Set the network parameters using the CCPASETX instruction or CCPASET instruction.
5.
Set the station number/IP address using the UINI instruction.
Setting range
• Parameter Editor
*1
• Program
(Default: Parameter Editor)
2 PARAMETER SETTINGS
2.2 Required Settings
2
97