Control Supply Module (CSM)
9.3 Interface description
from the specification, or an overtemperature condition, then the contact opens ("not OK"). The
Control Supply Module is shutdown if an overtemperature condition remains after this warning.
Table 9-3
Signaling contact without terminal connector in
the delivery condition
9.3.4
X24 24 V terminal adapter
Table 9-4
Type: Screw terminal 5 (Page 177)
The 24 V terminal adapter is included in the scope of supply.
9.3.5
S1 DIP switch
Table 9-5
It is only permissible to changeover when in the no-voltage state.
136
Installing the signaling contact
X24 24 V terminal adapter
Terminal
Function
+
24 V power supply
M
Ground
DIP switch S1
Terminal
Function
1
Changeover switch,
single operation / paral‐
lel operation
2
Dummy contact (not
used)
Signaling contact, complete with terminal connec‐
tor
Technical specifications
Supply voltage 24 ... 28.8 V DC
Electronics ground
Technical specifications
Left: Single operation
Right: Parallel operation
Changing over the output characteristic
-
System Manual, 10/2020, 6SL3097-5AH10-0BP0
High Frequency Drive